• 60 •
0
1
Integer
R/W
0
0
32767
2
Analog
R/W
8.0
22.0
35.0
3
Analog
R/W
8.0
19.0
35.0
4
Analog
R/W
0.0
20.0
100.0
5
Analog
R/W
8.0
35.0
35.0
6
Analog
R/W
8.0
15.0
35.0
7
Analog
R/W
0.0
0.0
100.0
8
Analog
R/W
0.0
100.0
100.0
9
Analog
R/W
0.0
0.0
100.0
10
Analog
R/W
0.0
100.0
100.0
11
Analog
R/W
0.0
0.0
100.0
12
Analog
R/W
0.0
~
100.0
13
Analog
R/W
0.0
~
100.0
14
Integer
R/W
0
0
65536
15
Integer
R/W
0
~
23
16
Integer
R/W
0
~
59
17
Integer
R/W
1
~
31
18
Integer
R/W
1
~
12
19
Integer
R/W
0
~
99
20
Analog
R/W
-99.9
-99.9
99.9
21
Analog
R/W
0.0
0.0
100.0
22
Analog
R/W
-99.9
-99.9
99.9
23
Analog
R/W
0.0
0.0
100.0
24
Integer
R/W
0
0
2000
25
Analog
R/W
0.0
0.0
100.0
26
Integer
R
0
~
65536
27
Integer
R
0
~
65536
28
Integer
R
0
~
65536
29
Integer
R
0
~
65536
30
Integer
R
0
~
65536
31
Integer
R
0
~
65536
32
Integer
R
0
~
65536
33
Analog
R
8.0
~
35.0
34
Analog
R/W
8.0
20.5
35.0
35
Analog
R
8.0
~
35.0
36
Integer
R
0
~
999
37
Analog
R
-99.9
~
99.9
38
Analog
R
-99.9
~
99.9
39
Analog
R
-99.9
~
99.9
40
Analog
R
-99.9
~
99.9
41
Analog
R
0.0
~
100.0
42
Analog
R
0.0
~
99.9
43
Analog
R
0.0
~
100.0
44
Analog
R
0.0
~
99.9
45
Integer
R
0
~
1000
46
Integer
R
0
~
2000
47
Analog
R
0.0
~
100.0
48
Analog
R
0.0
~
100.0
49
Analog
R
0.0
~
100.0
CLIMATIC RT_UNITARY-IOM-1508-E
BMS
@Address
R/W
DESCRIPTION
MIN
Fact.
MAX
bms, watchdog counter
control, bms day, set point of cooling mode
control, bms day, set point of heating mode
economizer, bms day, set point of minimum fresh air
control, bms night, set point of cooling mode
control, bms night, set point of heating mode
economizer, bms night, set point of minimum fresh air
control, bms day, set point of dehumidi
fi
cation
control, bms day, set point of humidi
fi
cation
control, bms night, set point of dehumidi
fi
cation
control, bms night, set point of humidi
fi
cation
blower, bms day, nominal threshold for air
fl
ow control
blower, bms night, nominal threshold for air
fl
ow control
power meter, value for reset memory
clock, hour setting
clock, minute setting
clock, day setting
clock, month setting
clock, year setting
emulation, value of the room temperature send by bms
emulation, value of the room humidity send by bms
emulation, value of the outside temperature send by bms
emulation, value of the outside humidity send by bms
emulation, value of the air quality send by bms
emulation, value of the speed blower send by bms
power meter, value of the real power
power meter, value of the reactive power
power meter, value of the power factor
power meter, value (weight low) of the real energy
power meter, value (weight high) of the real energy
power meter, value (weight low) of the reactive energy
power meter, value (weight high) of the reactive energy
control, set value of cooling mode
control, customer (dc/dm) set point
control, set value of heating mode
alarm, codes
control, value of the room temperature
control, value of the outside temperature
control, value of the supply temperature
control, value of the return temperature
control, value of the room humidity
control, calculated value of the room absolute humidity
control, value of the outside humidity
control, calculated value of the outside absolute humidity
blower, value of differential pressure sensor on air
fl
ow
economizer, value of air quality sensor
economizer, opening percentage send to the actuator
gas heaters, opening percentage calculated for the valve
electrical heaters, power percentage calculated for the triac
APPENDIX 1
Modbus, BACnet, Trend, Carel