CLIMATIC RT_UNITARY-IOM-1508-E
AIR MANAGEMENT
HUMIDITY SET POINT (OPTION)
Function
The CLIMATIC offers in option, the possibility to manage the relative humidity. The controller is programmed to maintain an humidity
as comfortable as possible with the most economic usage of the unit.
Description
The relative humidity is maintained between 2 thresholds (a minimum threshold corresponding to the point of humidi
fi
cation and a
maximum threshold corresponding to the point of dehumidi
fi
cation).
During dehumidifying mode:
•
The fan speed is forced on low speed threshold (
2329
).
•
If the Outside humidity is high (> dehumidifying setpoint (
2271
) - 10.0%hr) then Free-Cooling or Free-Heating is disabled and
the fresh air damper is closed.
During Humidi
fi
cation mode:
•
If the outside humidity is low (<humidifying setpoint (
2272
) + 10.0%hr) then Free-Cooling or FreeHeating is Disabled and the
damper is closed.
Settings
The different settings to adjust the
fl
ow control are available in the menu:
The dehumidi
fi
cation is ensured by the compressors in cooling mode or during the dead zone.
Note that if this function is activated, priority is given to the romm humidity contrôol instead of the room temperature control.
The humidi
fi
cation is ensured by a 0/10V signal controlled by a PI algorithm.
The humidi
fi
cation and deshumidi
fi
cation thresholds can be speci
fi
ed according to the scheduling and can take different mode for each
schedule mode (Night, Day, Day I, Day II and BMS).
Humidity mode
Humidi
fi ca
tion
Dead z
one
Dehumidi
fi ca
tion
Ambient humidity % (HR)
Day mode
60
Night mode
20
Day mode
60
Day I mode
50
Day I mode
50
Night mode
20
Day II mode
30
Setpoint to activate function
set point of dehumidi
fi
cation
set point of humidi
fi
cation
integral time control for dehumidi
fi
cation
integral time control for humidi
fi
cation