CBX32MV
Heat Pump Operation (Heating and Cooling)
Room thermostat
calls for first
stage?
Air Handler Control receives inputs on Y1 terminal
.
Y1 terminal on Control is configured as input and passes
signal from room thermostat to outdoor unit.
Y1 input to the Control will control the indoor blower
according to the cooling or heating mode blower speed,
ramping and adjust selection jumper pins.
Air Handler Control receives inputs on Y1 and O terminals
.
Y1 terminal on Control is configured as input and passes signal
from room thermostat to outdoor unit.
Y1 input to the Control. Will control the indoor blower
according to the cooling mode blower speed, ramping and
adjust selection jumper pins.
Room thermostat calls for
second stage?
Still calling for first
stage?
Y2 terminal on Control
is configured as input
and passes signal from
room thermostat to
outdoor unit.
Y2 terminal is an input
to the Control. The
indoor blower will be
controlled according
to the jumper pin
selections.
Still calling for second
stage?
De-energize Y2 terminal on Control.
Indoor blower speed will reset to Y1
demand.
De-energize Y1 (and O in cooling) terminals on
Control.
De-energize indoor blower per ramping profile.
No
Yes
Cooling
Air Handler Control Indoor Blower Mode Speed and Profiles settings
1.
Set
Cooling Mode Blower Speed
jumper pin . (Low and high indoor blower CFM settings are identical for
cooling and heat pump)
2.
Set Blower Adjust Selection jumper pin.
3.
Set Cooling Mode Blower Ramping jumper pin (Cooling calls - All ramping profiles are active) (Heating calls -
Only ramping profiles 1 and 2 are active. If profiles 3 or 4 are selected, Control will default to profile 1)
A
Profile 1 does not provide any ramping profiles.
B
Profile 2 provides a 30 second indoor blower ON delay at the start of a heat pump heating demand. (45
second indoor blower
OFF
delay)
4.
Simultaneous Heat Pump and electric heat call: Indoor Blower will operate at the highest CFM requested by
the heat pump or the electric heat blower speed selection.
Single or Two-Stage Unit
1.
Control on-board link must be cut between Y1 and Y2 to allow two stage cooling operation.
Heating
NOTE — The outdoor unit control directly controls the outdoor
unit operation.)
NOTE — The outdoor unit control directly controls the
outdoor unit operation.
NOTE — The outdoor unit control
directly controls the outdoor unit
operation.)
NOTE — The outdoor unit control directly controls
the outdoor unit operation.
NOTE — The outdoor
unit control directly
controls the outdoor
unit operation.)
Yes
Yes
Yes
Yes
No
No
2.
Control on-board link must be cut between R and O to allow heat pump operation.
CUT ON-BOARD LINK
Y1-Y2 FOR
TWO-STAGE A/C
Y1-Y2
2-STAGE
COMPR
R-O
HEAT
PUMP
R-DS
DEHUM
OR
HARMONY
CUT
FOR OPTION
CUT ON-BOARD
LINK R -O.
RECOMMEND
— USE FIGURE 19 AS A REFERENCE FOR SETTING
JUMPER CONFIGURATIONS ON THE AIR HANDLER CONTROL.
IMPORTANT
— USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE FIGURE 19,
CBX32MV JUMP AND LINK GUIDE FOR FURTHER
DETAILS.