Page 18
speed position #4 is 1000 CFM. The + adjustment setting for
that position is 1080 CFM and for the - adjustment setting is
910 CFM. After the adjustment setting has been determined,
choose the remaining speed jumper settings from those
offered in the table in that row.
The TEST pin is available to bypass the BDC3 control and
run the motor at approximately 70% to test that the motor is
operational. This is beneficial primarily in troubleshooting.
G must be energized for motor to run.
COOL JUMPER
The
COOL
jumper is used to determine the CFM during
either cooling or heat pump operation without a call for
electric heat. These jumper selections are activated for
cooling when Y2 and DS terminals in the Merit
®
CBX25UHV are energized. The are activated for heating
when Y2 is energized.
Applications
without
the Lennox ComfortSense
®
7000
thermostat will provide 70% of the
COOL
CFM during
first-stage cooling for two-stage outdoor units. 100% of
COOL
speed is provided for systems with a single-stage
outdoor unit.
Applications
with
the Lennox ComfortSense
®
7000
thermostat, but no demand for de-humidification will
operate as follows: during a first-stage cooling call
(two-stage outdoor unit), the air volume is 70% of the
COOL
jumper selection. This arrangement provides for
additional dehumidification during standard first-stage
cooling. See the tables that follow for various scenarios
concerning use of the ComfortSense
®
7000 thermostat
and the Merit
®
CBX25UHV series unit.
For applications with Harmony III
®
zone control, the air
handler CFM volume is determined by the Harmony III
control center. The minimum blower speed is
predetermined at 250 CFM for -018, -024, -030 and -036
units and 450 CFM for -042, -048 and -060 units. This
speed is not adjustable. See footnotes in the blower
performance tables.
With the thermostat set for
Continuous Fan
and without a
call for heating or cooling, the Merit
®
CBX25UHV provides
50% of the
COOL
CFM selected.
NOTE
- For two-stage heat pumps, air handler will operate
at 70% of the
COOL
selection until supplemental electric
heat is demanded. At that time, the air handler will operate
at the selected
HEAT
speed. This arrangement provides
warmer supply air during second-stage heating.
Table 3. Merit
®
CBX25UHV‐018 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First-Stage “COOL” Speed
Second-Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
470
670
890
1080
350
470
620
760
470
675
890
1090
NORM
440
615
810
1000
350
450
560
700
435
610
815
1020
–
400
560
730
910
350
420
520
650
400
575
725
915
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.
Table 4. Merit
®
CBX25UHV‐024 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First-Stage “COOL” Speed
Second-Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
470
690
900
1120
350
470
625
775
480
670
890
1125
NORM
430
640
810
1020
330
450
580
720
430
605
820
1020
–
410
550
720
900
300
405
505
650
390
545
740
930
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.