Page 19
MERIT
®
CBX25UHV SERIES
Table 5. Merit
®
CBX25UHV‐030 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First-Stage “COOL” Speed
Second-Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
650
900
1100
1320
430
600
740
920
650
875
1100
1330
NORM
590
795
1000
1200
390
550
680
830
580
800
1000
1200
–
520
730
895
1075
340
475
620
750
500
700
900
1090
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.
Table 6. Merit
®
CBX25UHV‐036 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First-Stage “COOL” Speed
Second-Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
880
1115
1345
1435
615
770
930
1090
880
1110
1340
1435
NORM
800
1010
1215
1425
555
695
845
990
795
1005
1215
1420
–
715
905
1095
1275
505
625
755
885
715
905
1090
1280
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.
Table 7. Merit
®
CBX25UHV‐042 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First-Stage “COOL” Speed
Second-Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
1115
1345
1560
1800
800
960
1120
1265
1130
1360
1580
1800
NORM
1025
1215
1415
1630
730
870
1020
1150
1040
1240
1450
1640
–
925
1110
1280
1460
650
790
915
1050
950
1120
1290
1470
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 450 cfm.