IOM / @DNOVA-µAC-0907-E - Page 9
cod. Description
P5= 1 P5= 2 P5= 3 P5= 4 P5= 5
E1
probe B1
auto
auto
man
auto
auto
E2
probe B2
auto
auto
man
auto
auto
E3
probe B3
auto
auto
man
auto
auto
E4
probe B4
auto
auto
man
auto
auto
EE
EEPROM run
man
man
man
man
man
EL
insuff. power on EEPROM write
man
man
man
man
man
H1
high pressure C1
man
man
man
man
man
H2
high pressure C2
man
man
man
man
man
L1
low pressure C1
man
auto
man
auto
auto
L2
low pressure C2
man
auto
man
auto
auto
F1
filter dirty
man
auto
man
man
auto
FL
flow
man
auto
man
man
man
CF
water flow
man
auto
man
auto
auto
r1
heating elements
man
man
man
man
man
At
supply temp
man
auto
man
man
man
AH
humidifier
man
auto
man
auto
auto
Lt
low temperature
man
auto
man
auto
auto
ht
high temperature prealarm
man
auto
man
auto
auto
Ht
high temperature
man
auto
man
auto
auto
LH
humidity
man
auto
man
auto
auto
HH
high humidity
man
auto
man
auto
auto
tC
comp. thermal
man
auto
man
man
auto
tF
fan thermal
man
auto
man
man
auto
t1
fan 1 thermal
man
auto
man
man
auto
t2
fan 2 thermal
man
auto
man
man
auto
AL
serious generic
Pb
Pb
Pb
Pb
Pb
FA
smoke-fire
man
auto
man
man
auto
pA
power fail (shelters)
auto
auto
auto
auto
auto
CL
clock
man
man
man
man
man
P6 Delta from the effective set point for low temperature
alarm
P7 Delta from the effective set point for high temperature
alarm
Sets the alarm threshold for low (Lt) and high (Ht) ambient
temperature. This value is specified as a differential in respect
to the effective setpoint, considering any compensation
operations (see parameters /1, rG, rH, Hc). These alarms, in
the case of automatic reset, have an hysteresis of 1 degree
and are generated only when the machine is active.
Range P6/P7: 0÷50°c 0÷90°F Def. P6/P7: 10
P8 Delta from set point for low humidity alarm
P9 Delta from set point for high humidity alarm
Sets the alarm threshold for low (LH) and high (HH) ambient
humidity. This value is specified as a differential in respect to
the effective setpoint. These alarms, in the case of automatic
reset, have an hysteresis of 1% and are generated only when
the machine is active and if the humidifier is present (for low
humidity alarm).
Range P8/P9: 0÷50 %rH Def. P8/P9: 20
PA High/low temperature/humidity alarm delay on start-
up
Sets the delay in recognising the high/low temperature and
humidity alarms on starting the machine, that is when switching
from STAND-BY => ON.
N.B. The low humidity alarm is delayed by the start-up of the
humidifier. This avoids low humidity alarms on resetting any
humidifier alarms.
Range: 0÷150 min Def.: 20
Pb type of management of generic alarm input ID5
Sets the type of alarm generated by input ID5 (AL). This
function is enabled only with parameter H2= 0 and can be
managed even with the machine in stand-by (see table on
general parameters P)
Range: 0÷6 flag Def.: 1
Pc Generic alarm delay
Sets the delay in activation of the generic alarm ID5 (AL). This
delay is refereed to the activation of the alarm itself.
Range: 0÷250s Def.: 60
DESCRIPTION AND CONFIGURATION OF THE PARAMETERS