c= compressor management parameters

c1 Minimum on time

Sets  the  minimum  activation  time  for  the  compressor, 

irrespective  of  request  (see  diagram  at  the  end  of  the 

paragraph).

Range: 0÷300s Def.: 60

c2 Minimum oFF time

Sets the minimum off time for the compressor, irrespective of 

request (see diagram at the end of the paragraph).

Range: 0÷900s Def.: 60

c3 Minimum time between two start-ups

Sets the minimum time between two successive start-ups of 

the same compressor, irrespective of request. This limits the 

number of start-ups by time (see diagram at the end of the 

paragraph).

Range: 0÷900s Def.: 360

c4  Minimum  time  between  the  start-up  of  two 

compressors

Sets the minimum time which must elapse between successive 

start-ups of 2 compressors (if configured for 2 comp.). Delaying 

the activation of the compressors avoids overloading the line 

due to close or simultaneous peaks.

Range: 0÷300s Def.: 30

c5 oFF delay between the two compressors

Sets the minimum time which must elapse between the shutting 

down of different compressors.

Range: 0÷300s Def.: 0

c6 compressor rotation

Allows the compressors to exchange priority for start-up and 

shut-down. 

0= rotation disabled

1= rotation enabled (with H5= 2 or 5).

The rotation is FIFO, that is the fist compressor to be switched 

on is the first to be switched off.

Range: 0÷1 flag Def.: 0

c7 comp. on delay from supply fan start-up

Sets the minimum time which must elapse between the start-up 

of the fan and the activation of the compressor.

Range: 0÷300s Def.: 20

c8 Hour counter threshold for compressor operation

Sets the number of hours of compressor operation beyond 

which the maintenance request is signalled.

0= this function is not handled.

Range: 0÷30000 hours Def.: 0

c9 Hour counter compressor 1

cA Hour counter compressor 2

Indicates  the  number  of  operating  hours  of  compressor  1 
and/or 2. Pressing the   and   buttons together during the 

display of this parameter resets the hour counter (only in USER 

or FACTORY mode) and cancels the maintenance request, if 

enabled. Management of the hour counter is suspended during 

the setting of the parameters, while the data is written to the 

EEPROM every 30 mins.

Range: 0÷30000 hours Def.: 0

F= fan management parameters

F1 Fan operating mode

This parameter imust be set to 0 during the setting of limits 

F2 and F3.

0= always ON

1= proportional speed regulation with minimum speed

2= proportional speed regulation with cut-off

The  values  1  or  2  indicate  operation  of  the  supply  fan  in 

proportional mode with Hb=0; if, on the other hand, phase-cut is 

used for the condensation fan with Hb= 1 or 2, operation is that 

described in the diagrams at the end of the paragraph. The fan 

is only activated when at least one of the compressors is on. 

In the case of condensation probe B3 malfunction, the fan is 

forced on at maximum speed, (F8), if the external temperature 

(B2) is greater than 15°C; on the other hand, if

the temperature is lower than 15°C, the fan operates at an 

average of the values F7 and F8.

Range: 0÷2 flags  Def.: 1

F2 Minimum triac voltage threshold

F3 Maximum triac voltage threshold

In the case of proportional fan speed regulation, installation 

of  the  power  board  MCHRTF*0A0  is  required.  In  this  case 

parameters F2 and F3 must be set to obtain at the output the 

minimum and maximum voltage, respectively, accepted by the 

motor used. The values set do not correspond to the effective 

voltage  in  Volts,  but  to  an  internal  calculation  of  the  µAC. 

With the CONV0/10A0 module, or with FCS3** three-phase 

regulators, set F2= 0 and F3= 100.

Range F2: 0÷F4 step Def. F2: 35

Range F3: F3÷100 step Def. F3: 75

F4 Duration of triac impulse

Represents the width, in milliseconds, of the on pulse of the 

triac. For inductive-type motors set F4= 2; on the other hand, 

for capacitative-type motors or with the CONV0/10A0 module, 

or with FCS3** three-phase regulators, set F4= 0.

Range: 0÷15ms Def.: 2

F5  Regulation  band  percentage  for  minimum  speed  or 

temp./pressure for minimum speed in condensation

F6 Regulation band percentage for maximum speed or 

temp./pressure for maximum speed in condensation

When fan speed regulation is used to control the main fan, 

F5 and F6 represent the percentage of the regulation band; 

when on the other hand it is used to control the condensation 

fan, F5 and F6 are absolute temperature or pressure values 

(see Fig. 7).

Warning: 

if  the  parameter  indicates  a  temperature,  this  is 

not  automatically  converted  to  Fahrenheit  on  changing  the 

parameter /C (see diagrams at the end of the paragraph).

Range F5: 0÷F6%, °c, °F F5: /4÷F6 bar Def. F5: 20

Range F6: F5÷100% F5÷158°c, °F F5÷/5 bar Def. F6: 100

F7 Minimum output value

Specifies  a  speed  value  above  the  minimum  value,  set 

using  the  parameter  F2.  (see  diagrams  at  the  end  of  the 

paragraph).

Range: 0÷F8% Def.: 10

DESCRIPTION AND CONFIGURATION OF THE PARAMETERS

Summary of Contents for @DNOVA 2mAC ADVANCED CONTROLLER

Page 1: ...Providing indoor climate comfort DNOVA AC IOM 0907 E Installation operating and maintenance DNOVA 2 AC ADVANCED CONTROLLER...

Page 2: ......

Page 3: ...rameters 7 Parameter modification 7 DESCRIPTION AND CONFIGURATION OF THE PARAMETERS 9 probe parameters 12 r regulation parameters 13 c compressor management parameters 16 F fan management parameters 1...

Page 4: ...rs can be configured not only using the keypad located on the front panel but also using a hardware key and or via serial line GENERAL CHARACTERISTICS General description The AC is an electronic contr...

Page 5: ...mbol off the Set point is displayed time band selected dehumidification active ventilation active fan speed cooling active number 1 or 2 cooling actuators opening cooling valve or in shelter mode open...

Page 6: ...the Factory parameters Pressed together for 2 secs reset the alarms Status indicators The main states of the regulator power supply present alarm active and remote ON OFF input status are displayed to...

Page 7: ...Hc Damper ON OFF Out4 Damper 2 Hc Out5 Supply fan Relay digital outputs Connector 3 Out 6 Alarm HF Out 7 Alarm HA Rotation control H2 Analogue outputs Connector 1 Y1 Damper output 2 Hc Y2 Condensatio...

Page 8: ...ia the master unit 1 sends the command to activate and deactivate the unit in stand by the command is updated every 10 minutes Heating element Air outlet Air inlet Air flow diverter Condenser air outl...

Page 9: ...arameter HL Level Access DIRECT D immediate access USER U access via password 22 parameter HH FACTORY F access via factory password 177 Parameter modification Accessing Direct parameters D The value o...

Page 10: ...ed while the and buttons can be used to modify such value Press enter again to temporarily store the new value Then using the and buttons scroll the parameters menu repeating the previous steps for ea...

Page 11: ...allows the key to be programmed with the machine s parameters During this operation the message EC is displayed and in the case of errors ECEE Adjusting LCD contrast The contrast of the display can b...

Page 12: ...mperature Set Point heating Minimum temperature set point also for compensation Maximum temperature setpoint also for compensation Minimum humidity set point Maximum humidity set point Type of tempera...

Page 13: ...on If used in condensation the fan is switched off below the value of F5 with an hysteresis of 0 5 bar for pressure or 1 C for temperature Minimum Triac voltage threshold Maximum Triac voltage thresho...

Page 14: ...U o M Var Def Pres U F F F 0 250 s 10 20 U F F F 0 90 s 1 5 U F F F 0 250 s 1 40 U U U U 0 15 min 1 0 F F F 1 5 flag 1 1 5 U F U U 0 50 90 C F 1 10 U F U U 0 50 90 C F 1 10 U F U U 0 50 rH 1 20 2 0 U...

Page 15: ...ling ON OFF with Out3 4 condensation control Function of probe B3 0 humidity control 1 condensation control ON OFF digital input 0 absent 1 present Alarm relay logic 0 de energised in alarm for all al...

Page 16: ...nge 10 0 10 0 rH bar Def 0 0 9 Calibration input B4 Corrects the value measured by B4 Range 6 0 6 0 C 10 8 10 8 F Def 0 0 A Digital filter Stabilises the coefficient used in the digital filtering of t...

Page 17: ...compensation of the set point using the external air probe this value also represents the lower limit for the excursion of the set point Range 20 rb C 4 rb F Def 0 rb Maximum temperature set point Lim...

Page 18: ...oo low temperature being sent into the room In the ED and CW configurations the actuators turn OFF progressively when the supply temperature falls below the m set the differential is fixed at 3 C Duri...

Page 19: ...ing of limits F2 and F3 0 always ON 1 proportional speed regulation with minimum speed 2 proportional speed regulation with cut off The values 1 or 2 indicate operation of the supply fan in proportion...

Page 20: ...Sets the operating time at maximum speed on starting up the fans if used for condensation control to overcome the mechanical inertia of the motor If set to 0 the function is not performed that is the...

Page 21: ...ature This value is specified as a differential in respect to the effective setpoint considering any compensation operations see parameters 1 rG rH Hc These alarms in the case of automatic reset have...

Page 22: ...lows ID7 24Vac Heating Set r9 ID7 0 Cooling Set r1 When the machine is in cooling mode the presence and the number of heating elements depends on parameter H6 in heating mode on the other hand the coo...

Page 23: ...minutes in stand by or time band sleep mode for a period of H7 2 seconds These procedures like the complete closing of the valve on instrument start up allow the degree of opening of the valve to be a...

Page 24: ...energised only for serious alarms Range 0 3 flags Def 0 HG Delay on start up Sets the delay time on each switching from stand by to ON or POWERON During this phase the green LED is on but all actuato...

Page 25: ...m the modifications made Time bands Entering the parameter rt see USER parameter modification allows the selection of rt 1 or 2 enabling the time band function Pressing the Sel button displays in sequ...

Page 26: ...wed by the Alarm button The code of the last alarm event is shown and on repeatedly pressing Sel the hour minute and the date The and buttons scroll the alarm data In places where no alarm has been re...

Page 27: ...board EEPROM and must be performed when installing the board itself The alarm codes displayed are those reported in the table in the chapter on the alarms in addition other special codes have been in...

Page 28: ...mm FC ON ON 34 nn counter fan imm FA ON ON serious alarms in the configuration with two alarm relays these activate the alarm output the other alarms ON the other hand activate the dehumidification In...

Page 29: ...ion of the compressor and causes its immediate switching off without waiting the corresponding delay times The alarm H2 is managed only if parameter H5 2 or 4 two independent circuits If condensation...

Page 30: ...PA shelter power failure alarm External power failure alarm delayed by 2 seconds This is generated for models configured as shelters when input ID6 is open it causes the immediate switching off of the...

Page 31: ...1 km Cables 1 twisted pair and shield AWG20 22 with capacity between leads 90pF m e g BELDEN 8761 8762 cables Protection against electric shock the device guarantees only a functional insulation betw...

Page 32: ...d Input ID1 for Remote ON OFF switches on the machine when powered Input ID7 for Cooling heating enables heating operation when powered Y1 0 10Vdc output not optically isolated from power supply poten...

Page 33: ......

Page 34: ...IOM 0907 E BELGIUM LUXEMBOURG CZECH REPUBLIC FRANCE GERMANY NETHERLANDS POLAND PORTUGAL RUSSIA SLOVAKIA SPAIN UKRAINE UNITED KINGDOM AND IRELAND OTHER COUNTRIES Due to Lennox s ongoing commitment to...

Reviews: