Lennox ADAGIO-EN Installation Instructions Manual Download Page 8

8

MINIMUM CLEARANCES TO 

COMBUSTIBLES

Appliance And Vent Clearances

The appliance is approved with zero clearance to com-

bustible materials on all sides (as detailed in 

Table 5)

with the following exception: 

When the unit is installed 

with one side flush with a wall, the wall on the other 

side of the unit must not extend beyond the front edge 

of the unit

. In addition, when the unit is recessed, the 

side walls surrounding the unit must not extend beyond 

the front edge of the unit (see 

Figure 3

).

12 (305) Mantel

10 (254) Mantel

8 (203) Mantel

6 (152) Mantel

4 (102) Mantel

16

(406)

12

(305)

10

(254)

2 (51) Mantel

Top Of

Appliance

6

(152)

8

(203)

Mantel Clearances

Inches (mm)

14

(356)

Combustible materials 

may project beyond the 

side of the fireplace 

opening as long as it is 

kept within the shaded 

area illustrated here.

At 14" minimum side 

wall clearance, a 

combustible wall may 

project to any length

Figure 10

17"

(432)

14" (356)

Min. Distance to 

Unprotected Side Wall

45

°

Combustible Materials Allowed

In Shaded Area “Safe Zone”

2” (51) Minimum

Clearance to Combustibles

12" (305)

5"

(127)

Min. Distance

8-1/4” (210) to 

Protected Side Wall

Top View Of

Fireplace

Side

Wall

Side

Wall

inches (millimeters)

Figure 9 - Mantel Clearances 

Side Wall Clearances

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Inches (millimeters)

Figure 8 - Minimum Shelf Height Above Fireplace

MODELS

Adagio-MN

Adagio-MP

Adagio-EN

Combustible Shelf Height

 Inches (millimeters)

Top Vent - with One 90 Degree Elbow

Secure Vent

Secure Flex (flex elbow)

*52 (1321)

*53-3/4 (1365)

* Includes 4” clearance to combustibles

  (required above vent components)

MINIMUM CLEARANCES

 Inches (millimeters)

Back

1/2 in. (13 mm)

Sides

1/2 in. (13 mm)**

Top Spacers

0 in. (0 mm)

Floor

0 in. (0 mm)***

From Bottom of Unit

To Ceiling

64 in. (1626 mm)

Vent

3 (76) 

Top 

*

1 (25.4) 

Sides & Bottom

SERVICE CLEARANCES 

Feet (meters)

Front

3 feet (0.9 meters)

Table 5

Do not insulate the

space between the

appliance and the

area above it.

*Shelf Height

(see table)

Shelf Above Fireplace - Top Vent

Drywall

Header

Top Spacers

4” 

 

(102mm)

u

 4" clearance is required above the elbow 

for installations that require an elbow at the 

top of the unit and that ends in a horizontal 

termination.

*  Note:  3 in. (75 mm) above any horizontal vent component. 

See Note

 

u

 in

 

Figure 8.

**  Note:

  

See Page 9, Step 1 for clearance requirements 

to the nailing flange located at each side of the unit and 

any screw heads adjacent to it.

*** Note

To ensure proper fit of the facade (required - sold 

separately). The appliance base will need to be elevated 

3/4" minimum above the floor to allow for the proper 

fit of the facade (i.e. use 3/4" board as platform).

Shelf Height

To  provide  for  the  lowest  possible  shelf  surface,  the 

venting attached to the top vent should be routed in a 

way to minimize obstructions to the space above the 

appliance.  Do not insulate the space between the appli-

ance and the area above it (see

 Figure 8

). The minimum 

height from the base of the appliance to the underside 

of combustible materials used to construct a utility shelf 

in this fashion is shown in the table in  

Figure 8

.

Wall Finishes / Surrounds / Mantels

Note: 

Combustible wall finish materials and/or surround 

materials must not be allowed to encroach the area defined 

by the appliance front face (black sheet metal). Never al-

low combustible materials to be positioned in front of or 

overlapping the appliance front face. 
Non-combustible materials, such as surrounds and other 

appliance trim, may be installed on the appliance front face 

with these exceptions: they must not cover any portion 

of the glass or the air gaps above the glass door. 
Vertical installation clearances to combustible mantels 

vary according to the depth of the mantel.    Mantels 

constructed  of  non-combustible  materials  may  be 

installed above the appliance opening as outlined in 

Figure 9

.

NOTE:

 We recommend the use of high temperature 

paint (rated 175° F or higher) on the underside of the 

mantel.

f i r e - p a r t s . c o m

Summary of Contents for ADAGIO-EN

Page 1: ...isseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur...

Page 2: ...ssories that will require electrical power are to be installed the electrical power must be provided at the time of appliance installation The Electronic appliances have an electronic intermittent pil...

Page 3: ...Electrical Code CSA C22 1 latest edition Provide adequate clearances around air open ings and adequate accessibility clearance for service and proper operation Never obstruct the front openings of th...

Page 4: ...edition NOTE Flame appearance will diminish 4 per thousand feet Burner Orifice Sizes Elevation 0 4500 feet 0 1372 meters Model Nat Gas drill size inches Propane drill size inches Adagio 000 51 H0922...

Page 5: ...and wherever cold air could enter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line ho...

Page 6: ...tional Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CSA B149 1 in Canada Vertical Vent Termination Clearances Terminatemultipleventterminationsaccording to the installation cod...

Page 7: ...r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i...

Page 8: ...insulate the space between the appliance and the area above it Shelf Height see table Shelf Above Fireplace Top Vent Drywall Header Top Spacers 4 102mm u4 clearance is required above the elbow for ins...

Page 9: ...upport Thefireplaceshouldbesecuredtothesidefram ingmembersusingtheunit snailingflangeson each side of the fireplace front see Figure 11 Use 8d nails or their equivalent Figure 11 Left Side Front Corne...

Page 10: ...nce below the vent This does not include the suggested 1 4 rise per foot for horizontal runs With the facade installed required sold separately the appliancebasewillneedtobeelevatedaminimumof3 4 above...

Page 11: ...o change or discontinuance without notice With the facade installed required sold separately the appliance base will need to be elevated a minimum of 3 4 above the floor to allow for the proper fit of...

Page 12: ...sooting severe delayed ignition orothermalfunctions Anydamageresulting from an improper installation such as this is not covered under the limited warranty Never use galvanized or plastic pipe Refer...

Page 13: ...on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple ap pliances and must never be connected to a flue servingasolidfuelburningappliance The vent...

Page 14: ...5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0...

Page 15: ...of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer...

Page 16: ...ulk ing or mastic around the circumference of the joint to provide a water tight seal Figure 22 Storm Collar Flashing Figure 23 If the vent system extends more than 5 1 5 m above the roof flashing sta...

Page 17: ...VF uCeiling Firestop Spacer SV4 5VF u Ceiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4...

Page 18: ...nces for elbows as indicated in Figure 20 on Page 16 Maintain a minimum 1 25 mm clearance to combustibles on the vertical sections Clear ances for the horizontal runs are 3 76 mm on top 1 25 mm on sid...

Page 19: ...vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as describedinStepB Assembletheventsystem topointwheretheterminusofthelastse...

Page 20: ...1 V to 5 H ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system see Figure 30 AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VER...

Page 21: ...f 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 30 V H H1 V1 Wall Firestop Spacer SV4 5HF Ceiling Firestop Spa...

Page 22: ...ck out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent...

Page 23: ...U P 2 1 N E E R G BLUE 20 BLACK 16 WHITE FIELD WIRED FACTORY WIRED Turn The Appliance Mounted ON OFF Burner Control Switch To The OFF Position If An Optional Control Switch Is Installed Optional Blowe...

Page 24: ...ns provided with the kit If the blower kit is to be installed at the time of installationoratalaterdate themainpowersup plyandwallswitchmustbeinstalledatthetimeof installation This will require that t...

Page 25: ...ions provided in the Care and Operation Manual For piezo igniter location see Figure 40 on Page 24 millivolt appliances only Note LightingInstructionsarealsofoundonthe literature tag tied to the gas p...

Page 26: ...installation has been completed the gas line connected and tested for leaks and the initial burner operation has been checked out The size and position of the log set was engi neered to give the appli...

Page 27: ...ole on the bottom of log D over pin 3 4 Place the right front log E as shown in Figure 47 Position the hole on the bottom of log E over pins 4 and 5 6 Ember Placement Separate the Embers rockwool into...

Page 28: ...ner when installing the door Take care when seat ing the top door gasket so that it is not obstructed by the refractory panel If the doorfeelsrestrictedwhenlatching thetop door gasket may not be prope...

Page 29: ...rod and associated adjustable air shutter is patented technology Flame ad justments can be made quickly and accurately to taste without the need of disassembling the appliance and waiting for 30 minut...

Page 30: ...equirements Wall Details Complete finished interior wall To install the appliance facing flush with the finished wall position framework to accommodate the thickness of the finished wall Figure 54 u 4...

Page 31: ...ntrelasetiquetasadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeel...

Page 32: ...750 247M Vent Sections ListedSecureFlex Components Cat No Model Description These termination kits include firestop spacer gear clamps and flex adaptor H1969 SF4 5HT 2 HorizontalSquareTermina tion wit...

Page 33: ...anufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproductionofcarbon monoxid...

Page 34: ...t Orifice Thermopile on millivolt pilot assem blies only Millivolt Electronic Pilot Assemblies SIT Electronic Pilot Pilot Orifice B Retrieve the burner and slide the venturi tube over the orifice see...

Page 35: ...35 NOTES fire parts com...

Page 36: ...oducts reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fir...

Reviews: