NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

25

     

WARNING

Never use an open flame to 

check for leaks.

Turn on gas supply and test for gas leaks using a 

gas leak test solution (also referred to as bubble 

leak solution).  

Note: 

Using a soapy water solu-

tion is an effective leak test solution but it is not 

recommended, because the soap residue that is 

left on the pipes/fittings can result in corrosion 

over time. 

A. Light the appliance (refer to the lighting instruc-

tions label in control compartment or care and 

operation manual).

B. Brush all joints and connections with the gas 

leak test solution to check for leaks. If bubbles 

are formed, or gas odor is detected, turn the 

gas  control  knob  (off/pilot/on)  to  the  “OFF” 

position.  Either tighten or refasten the leaking 

connection, then retest as described above.

C. When the gas lines are tested and leak free be 

sure to rinse off the leak testing solution. 

TEST ALL CONNECTIONS FOR GAS LEAKS 

(FACTORY AND FIELD):

ELECTRONIC

Flame

Sensor

Hood

Igniter Rod

Pilot

Nozzels

Figure 42

Figure 41

MILLIVOLT

Thermocouple

Hood

Igniter Rod

3/8" Min

(9 mm)

Thermopile

Pilot

Nozzels

Step 7. VERIFYING APPLIANCE OPERA-

TION

Turn on burner then observe the individual 

tongues of flame on the burner.  Make sure 

all ports are open and producing flame evenly 

across the burner.  If any ports are blocked, or 

partially blocked, clean out the ports.

With gas line installed run initial system check-

out before closing up the front of the unit.  Follow 

the pilot lighting instructions provided in the 

Care and Operation Manual. For piezo igniter 

location see 

Figure 40 on Page 24 

(millivolt 

appliances only).

Note: 

Lighting Instructions are also found on the 

literature tag tied to the gas piping next to the 

gas valve. To access the tag, open the bottom 

control panel (see instruction sheet provided 

with the facade kit for additional information 

about  the  control  panel).  See

  Figure  40   on 

Page 24

When first lighting the appliance, it will take 

a  few  minutes  for  the  line  to  purge  itself  of 

air.  Once  purging  is  complete,  the  pilot  and 

burner  will  light  and  operate  as  indicated  in 

the  instruction  manual.  Subsequent  lighting 

of the appliance will not require such purging. 

Inspect the pilot flame (remove logs, if neces-

sary, handling carefully).

Millivolt Appliance Checkout

The  pilot  flame  should  be  steady,  not  lifting 

or floating. Flame should be blue in color with 

traces of orange at the outer edge.

The  top  3/8"  (10  mm)  at  the  pilot  generator 

(thermopile) and the top 1/8" minimum (tip) 

of the quick drop out thermocouple should be 

engulfed in the pilot flame. 

Electronic Appliance Checkout

Electronic Appliance Checkout

To light the burner, turn ‘ON’ the optional remote 

wall  switch  or  turn  the  appliance  mounted 

ON/OFF switch to the “ON” position.  Ensure 

the  igniter  lights  the  pilot.    The  pilot  flame 

should engulf the flame sensor as shown in 

Figure 42

.

The flame should project 1" (25 mm) beyond the 

pilot hood at all three ports 

(Figure 41).  

 Replace 

logs if removed for pilot inspection.

To light the burner; rotate the gas valve control 

knob  counterclockwise  to  the  “ON”  posi-

tion  and  turn “ON” the appliance mounted 

ON/OFF switch (or optional remote switch, if 

installed).

f i r e - p a r t s . c o m

Summary of Contents for ADAGIO-EN

Page 1: ...isseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur...

Page 2: ...ssories that will require electrical power are to be installed the electrical power must be provided at the time of appliance installation The Electronic appliances have an electronic intermittent pil...

Page 3: ...Electrical Code CSA C22 1 latest edition Provide adequate clearances around air open ings and adequate accessibility clearance for service and proper operation Never obstruct the front openings of th...

Page 4: ...edition NOTE Flame appearance will diminish 4 per thousand feet Burner Orifice Sizes Elevation 0 4500 feet 0 1372 meters Model Nat Gas drill size inches Propane drill size inches Adagio 000 51 H0922...

Page 5: ...and wherever cold air could enter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line ho...

Page 6: ...tional Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CSA B149 1 in Canada Vertical Vent Termination Clearances Terminatemultipleventterminationsaccording to the installation cod...

Page 7: ...r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i...

Page 8: ...insulate the space between the appliance and the area above it Shelf Height see table Shelf Above Fireplace Top Vent Drywall Header Top Spacers 4 102mm u4 clearance is required above the elbow for ins...

Page 9: ...upport Thefireplaceshouldbesecuredtothesidefram ingmembersusingtheunit snailingflangeson each side of the fireplace front see Figure 11 Use 8d nails or their equivalent Figure 11 Left Side Front Corne...

Page 10: ...nce below the vent This does not include the suggested 1 4 rise per foot for horizontal runs With the facade installed required sold separately the appliancebasewillneedtobeelevatedaminimumof3 4 above...

Page 11: ...o change or discontinuance without notice With the facade installed required sold separately the appliance base will need to be elevated a minimum of 3 4 above the floor to allow for the proper fit of...

Page 12: ...sooting severe delayed ignition orothermalfunctions Anydamageresulting from an improper installation such as this is not covered under the limited warranty Never use galvanized or plastic pipe Refer...

Page 13: ...on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple ap pliances and must never be connected to a flue servingasolidfuelburningappliance The vent...

Page 14: ...5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0...

Page 15: ...of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer...

Page 16: ...ulk ing or mastic around the circumference of the joint to provide a water tight seal Figure 22 Storm Collar Flashing Figure 23 If the vent system extends more than 5 1 5 m above the roof flashing sta...

Page 17: ...VF uCeiling Firestop Spacer SV4 5VF u Ceiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4...

Page 18: ...nces for elbows as indicated in Figure 20 on Page 16 Maintain a minimum 1 25 mm clearance to combustibles on the vertical sections Clear ances for the horizontal runs are 3 76 mm on top 1 25 mm on sid...

Page 19: ...vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as describedinStepB Assembletheventsystem topointwheretheterminusofthelastse...

Page 20: ...1 V to 5 H ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system see Figure 30 AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VER...

Page 21: ...f 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 30 V H H1 V1 Wall Firestop Spacer SV4 5HF Ceiling Firestop Spa...

Page 22: ...ck out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent...

Page 23: ...U P 2 1 N E E R G BLUE 20 BLACK 16 WHITE FIELD WIRED FACTORY WIRED Turn The Appliance Mounted ON OFF Burner Control Switch To The OFF Position If An Optional Control Switch Is Installed Optional Blowe...

Page 24: ...ns provided with the kit If the blower kit is to be installed at the time of installationoratalaterdate themainpowersup plyandwallswitchmustbeinstalledatthetimeof installation This will require that t...

Page 25: ...ions provided in the Care and Operation Manual For piezo igniter location see Figure 40 on Page 24 millivolt appliances only Note LightingInstructionsarealsofoundonthe literature tag tied to the gas p...

Page 26: ...installation has been completed the gas line connected and tested for leaks and the initial burner operation has been checked out The size and position of the log set was engi neered to give the appli...

Page 27: ...ole on the bottom of log D over pin 3 4 Place the right front log E as shown in Figure 47 Position the hole on the bottom of log E over pins 4 and 5 6 Ember Placement Separate the Embers rockwool into...

Page 28: ...ner when installing the door Take care when seat ing the top door gasket so that it is not obstructed by the refractory panel If the doorfeelsrestrictedwhenlatching thetop door gasket may not be prope...

Page 29: ...rod and associated adjustable air shutter is patented technology Flame ad justments can be made quickly and accurately to taste without the need of disassembling the appliance and waiting for 30 minut...

Page 30: ...equirements Wall Details Complete finished interior wall To install the appliance facing flush with the finished wall position framework to accommodate the thickness of the finished wall Figure 54 u 4...

Page 31: ...ntrelasetiquetasadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeel...

Page 32: ...750 247M Vent Sections ListedSecureFlex Components Cat No Model Description These termination kits include firestop spacer gear clamps and flex adaptor H1969 SF4 5HT 2 HorizontalSquareTermina tion wit...

Page 33: ...anufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproductionofcarbon monoxid...

Page 34: ...t Orifice Thermopile on millivolt pilot assem blies only Millivolt Electronic Pilot Assemblies SIT Electronic Pilot Pilot Orifice B Retrieve the burner and slide the venturi tube over the orifice see...

Page 35: ...35 NOTES fire parts com...

Page 36: ...oducts reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fir...

Reviews: