background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

Figure 17

10-1/2" Min. 

(267 mm)

10-1/2" Min. 

(267 mm)

Ceiling Framing

Plumb Bob

To attach a vent component to the appliance 

collar,  align the  dimpled end over  the collar, 

adjusting  the  radial  alignment  until  the  four 

locking  dimples  are  aligned  with  the  inlet  of 

the four inclined channels on the collar (refer to 

Figure 18

).  Push the vent component against 

the collar until it fully engages, then twist the 

component  clockwise,  running  the  dimples 

down and along the incline channels until they 

seat at the end of the channels.

The unitized design of the Secure Vent com-

ponents  will  engage  and  seal  both  the  inner 

and outer pipe without the need for sealant or 

screws.  If desired a #6 x 1/2" screw may be 

used at the joint, but it is not required as the 

pipe will securely lock when twisted.

C. Attach vent components to each other - Other 

vent sections may be added to the previously 

installed section in accordance with the require-

ments of the vertical vent figures and tables.  

To add another vent component to a length of 

vent run, align the dimpled end over the inclined 

channel end of the previously installed section, 

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four 

incline channels of the previous section. 

B.  Attach  vent  components  to  appliance 

- Secure Vent SV4.5 direct-vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connections (see 

Figure 18

).

All of the appliances covered in this document 

are fitted with collars having locking inclined 

channels. The dimpled end of the vent compo-

nents fit over the appliance collar to create the 

positive twist lock connection.

Align the dimple (four places) of the 

upper vent section with the opening 

of the locking incline channel on the 

lower vent section or appliance col-

lar.  Twist vent component clockwise 

to engage and seal until arrow and 

dimple align.

Dimple

Locking Incline 

Channel

Connected Vent 

Sections

Arrow

Arrow

Appliance Collar or 

Vent Section

Figure 18

Push the vent component against the previous 

section  until  it  fully  engages,  then  twist  the 

component clockwise running the dimples down 

and along the incline channels until they seat at 

the end of the channels. This seating position 

is indicated by the alignment of the arrow and 

dimple as shown in 

Figure 18.

D.  Install  firestop/spacer  at  ceiling  -  When 

using Secure Vent, use SV4.5VF firestop/spacer 

at ceiling joists; when using Secure Flex, use 

SF4.5VF firestop/spacer. If there is living space 

above the ceiling level, the firestop/spacer must 

be installed on the bottom side of the ceiling. 

If attic space is above the ceiling, the firestop/

spacer  must  be  installed  on  the  top  side  of 

the joist. 

 

Route the vent sections through the 

framed opening and secure the firestop/spacer 

with 8d nails or other appropriate fasteners at 

each  corner.  Remember  to  maintain  1"  (25 

mm)  clearance  to  combustibles,  framing 

members,  and  attic  or  ceiling  insulation 

when running vertical chimney sections. Attic 

insulation shield may be used to obtain the 

required  clearances  indicated  here  (order 

H3907,  SV4.5ARSA,  Attic  insulation  shield 

with  adjustable  height  from  12"-22").  See 

installation  accessories  table  on 

Page  32

.  

The gap between the vent pipe and a vertical 

firestop can be sealed with non-combustible 

caulking.

E. Support the vertical vent run sections -

Note - 

Proper venting support is very important. 

The weight of the vent must not be supported 

by the fireplace in any degree. 

Support  the  vertical  portion  of  the  venting 

system every 8 feet (2.4m) above the fireplace 

vent outlet.

Figure 19

Blocking

Support Straps

(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4 

mm) minimum 

clearance to 

combustibles

Roof Framing

Vertical (Offset) Installation

Analyze  the  vent  routing  and  determine  the 

quantities of vent sections and number of el-

bows required. Refer to Vertical Vent Figures 

and Tables on 

Page 17

 to select the type of 

vertical installation desired. Vent sections are 

available  in  net  lengths  of  4-1/2"  (114  mm), 

10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" 

(876 mm) and 46-1/2" (1181 mm).  Refer to the 

Vent Section Length Chart on 

Page 14

 for an 

aid in selecting length combinations. Elbows are 

available in 90° and 45° configurations. Refer 

to 

Figure 20

 for the SV4.5E45 and SV4.5E90 

elbow dimensional specifications.

Where  required,  a  telescopic  vent  section  

(SV4.5LA)  may be used to provide the installer 

with an option in installing in tight and  confined 

spaces or where the vent run made up of fixed 

length pieces develops a joint in a undesirable 

location, or will not build up to the required 

length. The SV4.5LA Telescopic Vent Section 

has an effective length of from 1-1/2" (38 mm) 

to 7-1/2 " (191 mm). The SV4.5LA  is fitted with 

a locking inclined channel end (identical to a 

normal vent section component) and a plain end 

with 3 pilot holes. Slip the plain end over the 

locking channel end of  a standard  SV4.5 vent 

component the required distance and secure 

with three screws.

Maintain  a  minimum  1"  (25  mm)  clear-

ance  to  combustible  materials  for  all 

vertical  vent  components.  Clearances  for 

all  horizontal  vent  components  are  3"  

(76 mm) on top, 1" (25 mm) on sides and 1"  

(25 mm) on the bottom.

A. Frame ceiling opening - Use a plumb line 

from the ceiling above the appliance to locate 

center of the vertical run. Cut and/or frame an 

opening,  10-1/2"  x  10-1/2"    (267  mm  x  267 

mm) inside dimensions, about this center mark 

(

Figure 17)

.

f i r e - p a r t s . c o m

Summary of Contents for ADAGIO-EN

Page 1: ...isseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur...

Page 2: ...ssories that will require electrical power are to be installed the electrical power must be provided at the time of appliance installation The Electronic appliances have an electronic intermittent pil...

Page 3: ...Electrical Code CSA C22 1 latest edition Provide adequate clearances around air open ings and adequate accessibility clearance for service and proper operation Never obstruct the front openings of th...

Page 4: ...edition NOTE Flame appearance will diminish 4 per thousand feet Burner Orifice Sizes Elevation 0 4500 feet 0 1372 meters Model Nat Gas drill size inches Propane drill size inches Adagio 000 51 H0922...

Page 5: ...and wherever cold air could enter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line ho...

Page 6: ...tional Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CSA B149 1 in Canada Vertical Vent Termination Clearances Terminatemultipleventterminationsaccording to the installation cod...

Page 7: ...r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i...

Page 8: ...insulate the space between the appliance and the area above it Shelf Height see table Shelf Above Fireplace Top Vent Drywall Header Top Spacers 4 102mm u4 clearance is required above the elbow for ins...

Page 9: ...upport Thefireplaceshouldbesecuredtothesidefram ingmembersusingtheunit snailingflangeson each side of the fireplace front see Figure 11 Use 8d nails or their equivalent Figure 11 Left Side Front Corne...

Page 10: ...nce below the vent This does not include the suggested 1 4 rise per foot for horizontal runs With the facade installed required sold separately the appliancebasewillneedtobeelevatedaminimumof3 4 above...

Page 11: ...o change or discontinuance without notice With the facade installed required sold separately the appliance base will need to be elevated a minimum of 3 4 above the floor to allow for the proper fit of...

Page 12: ...sooting severe delayed ignition orothermalfunctions Anydamageresulting from an improper installation such as this is not covered under the limited warranty Never use galvanized or plastic pipe Refer...

Page 13: ...on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple ap pliances and must never be connected to a flue servingasolidfuelburningappliance The vent...

Page 14: ...5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0...

Page 15: ...of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer...

Page 16: ...ulk ing or mastic around the circumference of the joint to provide a water tight seal Figure 22 Storm Collar Flashing Figure 23 If the vent system extends more than 5 1 5 m above the roof flashing sta...

Page 17: ...VF uCeiling Firestop Spacer SV4 5VF u Ceiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4...

Page 18: ...nces for elbows as indicated in Figure 20 on Page 16 Maintain a minimum 1 25 mm clearance to combustibles on the vertical sections Clear ances for the horizontal runs are 3 76 mm on top 1 25 mm on sid...

Page 19: ...vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as describedinStepB Assembletheventsystem topointwheretheterminusofthelastse...

Page 20: ...1 V to 5 H ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system see Figure 30 AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VER...

Page 21: ...f 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 30 V H H1 V1 Wall Firestop Spacer SV4 5HF Ceiling Firestop Spa...

Page 22: ...ck out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent...

Page 23: ...U P 2 1 N E E R G BLUE 20 BLACK 16 WHITE FIELD WIRED FACTORY WIRED Turn The Appliance Mounted ON OFF Burner Control Switch To The OFF Position If An Optional Control Switch Is Installed Optional Blowe...

Page 24: ...ns provided with the kit If the blower kit is to be installed at the time of installationoratalaterdate themainpowersup plyandwallswitchmustbeinstalledatthetimeof installation This will require that t...

Page 25: ...ions provided in the Care and Operation Manual For piezo igniter location see Figure 40 on Page 24 millivolt appliances only Note LightingInstructionsarealsofoundonthe literature tag tied to the gas p...

Page 26: ...installation has been completed the gas line connected and tested for leaks and the initial burner operation has been checked out The size and position of the log set was engi neered to give the appli...

Page 27: ...ole on the bottom of log D over pin 3 4 Place the right front log E as shown in Figure 47 Position the hole on the bottom of log E over pins 4 and 5 6 Ember Placement Separate the Embers rockwool into...

Page 28: ...ner when installing the door Take care when seat ing the top door gasket so that it is not obstructed by the refractory panel If the doorfeelsrestrictedwhenlatching thetop door gasket may not be prope...

Page 29: ...rod and associated adjustable air shutter is patented technology Flame ad justments can be made quickly and accurately to taste without the need of disassembling the appliance and waiting for 30 minut...

Page 30: ...equirements Wall Details Complete finished interior wall To install the appliance facing flush with the finished wall position framework to accommodate the thickness of the finished wall Figure 54 u 4...

Page 31: ...ntrelasetiquetasadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeel...

Page 32: ...750 247M Vent Sections ListedSecureFlex Components Cat No Model Description These termination kits include firestop spacer gear clamps and flex adaptor H1969 SF4 5HT 2 HorizontalSquareTermina tion wit...

Page 33: ...anufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproductionofcarbon monoxid...

Page 34: ...t Orifice Thermopile on millivolt pilot assem blies only Millivolt Electronic Pilot Assemblies SIT Electronic Pilot Pilot Orifice B Retrieve the burner and slide the venturi tube over the orifice see...

Page 35: ...35 NOTES fire parts com...

Page 36: ...oducts reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fir...

Reviews: