GB
R450 Values
Pressure switch setting sheet
Designation
Abbreviation Temperature °C
Cut-off in bar
Interlocking in bar
General safety LP switch
BPG
-26,0
0,02
0,72
Compressor safety HP switch 1
HPS1
68
17,00
13,00
Regulated LP switch 1
BPR1
-8
0,47
1,17
Compressor safety HP switch 2
HPS2
68
17,00
13,00
Regulated LP switch 2
BPR2
-9
0,39
1,09
LP frame switch
BPE
2,0
1,45
2,1
HP frame switch
HPE
50,0
8,18
12,2
Adjust the thermal magnetic circuit breakers GV(x) according to the values shown in the wiring diagram on page 6
or 7
Disconnect all circuit-breakers in the electrical cabinet
Set the KT7 delay time to 30 minutes, ie the top slider for 6 to 60 minutes and the bottom slider on 5
Set the KT1 delay time to 6 minutes, ie the top slider for 1 to 10 minutes and the bottom slider 6
Set the KT2 delay time to 7mn, ie the top slider for 1 to 10 min and the bottom slider 7
Equip yourself with your electrical PPE
Close the main disconnect switch
Check the voltage before and after of the disconnect switch and before of all circuit-breakers
Using the phase controller check the order of these, the direction must be clockwise otherwise the compressors
will be irreversibly damaged.
Close the control circuit breaker Q77 (both condenser fans will run after 30 minutes if the low pressure (LP) is
higher than the BPE switch-on value. To avoid this, lower the LP
pressure below the BPE and the HP pressure below
HPE)
Close transformer circuit breaker QF2
Adjust the fluid used in the P RACK controller by following the instructions below
Summary of Contents for FRIGA-BOHN DUO CU 114
Page 2: ...441 DUO CU 2 72 FR Caract ristiques dimensionnelles DUO CU A DUO CU C...
Page 24: ...441 24 72 DUO CU GB Dimensional characteristics DUO CU A DUO CU C...
Page 38: ...441 38 72 DUO CU GB Annex 3 Instructions of the oil level regulator TraxOil OM3 230V...
Page 46: ...441 46 72 DUO CU SP Caracter sticas dimensionales DUO CU A DUO CU C...
Page 56: ...441 56 72 DUO CU SP...
Page 69: ...DUO CU 69 72 Sch ma frigorifique refrigeration diagram diagrama de refrigeraci n...
Page 70: ...441 70 72 DUO CU...