441
34/72 -
DUO CU
GB
SHUTDOWN OF THE CONTROLLER
It is necessary to switch off the regulator for the fluid change: switch the installation to Manual (auto/manual switch) and
then press the reset button.
ACCESS THE MAIN MENU:
Click on "Menu": the code is 0000 (click on "enter" to validate a digit)
MODIFICATION OF THE COMPRESSOR FLUID
Find the Compressor menu, use the arrows
▲
and
▼
then confirm with the arrow
◄
(ENTER):
1.
Menu
2.
Compressors
3.
Configuration
4.
Scroll down the submenu to CAF04 mask concerning the fluid
5.
Enter the setting with the arrow
◄
(ENTER)
6.
Use the arrows
▲
and
▼
to find the desired fluid and confirm with the arrow
◄
(ENTER).
The cursor is repositioned at the top left
Fluid to select according to the fluid used:
Fluid used
R404A
R407A
R407F
R134A
R448A
R449A
R450A
R513A
Compressor fluid
R404A
R407A
R407F
R134A
R407F
R407F
R423A
R413A
7.
Return to the main menu by pressing the ESC key (normally 2x)
CONTROLLER WORKING
CONTROLLER OFF
Summary of Contents for FRIGA-BOHN DUO CU 114
Page 2: ...441 DUO CU 2 72 FR Caract ristiques dimensionnelles DUO CU A DUO CU C...
Page 24: ...441 24 72 DUO CU GB Dimensional characteristics DUO CU A DUO CU C...
Page 38: ...441 38 72 DUO CU GB Annex 3 Instructions of the oil level regulator TraxOil OM3 230V...
Page 46: ...441 46 72 DUO CU SP Caracter sticas dimensionales DUO CU A DUO CU C...
Page 56: ...441 56 72 DUO CU SP...
Page 69: ...DUO CU 69 72 Sch ma frigorifique refrigeration diagram diagrama de refrigeraci n...
Page 70: ...441 70 72 DUO CU...