8.5
Wiring test
Sensor wiring (Sensor
<n>
=1,2,3) can be checked as following:
1. Set function switch to PROG.
2. Enter sequence
****
.
Sensor contact in alarm position
Sensor contact back to idle
3. Set function switch to OFF.
8.5.1
Sensor-1: Alarm
Symptom
Cause and /or remedy
Sensor contact has been initiated, but alarm
has not been passed on
Sensor-1 alarm only enabled on selection switch position II
Sensor-1 alarm inactive during waiting period (LED indicator is green
permanently)
Sensor-1 monitoring temporarily deactivated
8.5.2
Sensor-1: Misuse-protection filter
Symptom
Cause and /or remedy
Misuse-protection filter does not work
Misuse protection filtering is only enabled on selection switch position
III
Misuse signal was not detected, because signal change was to short
(plus < 5 seconds)
8.5.3
Sensor-2: Emergency-button
Symptom
Cause and /or remedy
Inverse operation function
Incorrect contact type
8.5.4
Sensor-3: Technical alarm
Symptom
Cause and /or remedy
Sensor contact has been initiated, but alarm
has not been passed on
Sensor-3 alarm inactive during waiting period (LED indicator is green
permanently)
24
<n>
activated
<n>
deactivated