9.12
Sensor-2: Emergency-button
The button must be floating (potential free), i.e. separate from the alarm horn contact. When you use the unipolar button of
an existing installation use accessories EA-NT-IN
To verify contact type set function switch to
PROG
and enter
****
.
When pressing button, you should hear , back to idle . . Otherwise adjust contact type:
The setting of the jumper / switch is necessary for emergency operation powered from the telephone line, if battery and
supply should fail simultaneously. In this mode EasyAlarm® can only call the first phone number, without any
announcements. In case of wrong setting the permanently current may block the telephone line.
9.12.1
Contact type selection for new EasyAlarm® from Serial-number 90'000
For alarm units with serial-No. 90'000 ONLY the slide switch must be set
Do NOT adjust software!
Normally open contact (
Factory setting
)
Normally closed contact
Set slide switch inside battery compartment to
NO
Set slide switch inside battery compartment to
NC
9.12.2
Software selection for EasyAlarm® up to Serial-number 89'999
For units up to serial-No. 89'999 you need to program appropriated value according table below and set slide switch slide/
jumper. The emergency-contact type can be read or modified as follows:
*9713
60
##
*
Value
#
Value Info (
Factory setting
)
Value Info
33
Normally open contact
from Serial-No. 57'100 to 89'999:
Set slide switch inside battery compartment to
NO
from Serial-No: 50'000 to 57'099:
Jumper on PCB away from speaker (left position)
Leiterplatte
PCB
NO
Jumper
35
Normally closed contact
from Serial-No. 57'100 to 89'999:
Set slide switch inside battery compartment to
NC
from Serial-No: 50'000 to 57'099:
Jumper on PCB towards speaker (right position)
Leiterplatte
PCB
NC
Jumper
9.12.3
Activation time for emergency button
EasyAlarm® triggers an emergency call only if the button has been activated longer as certain time. This time can be read
out or modified as follows:
*9713
79
##
*
Value
#
Value Info
1..255 Contact time in steps of 20 ms. (
Factory setting: 50
*20 ms = 1000 ms = 1 s)
9.13
Sensor-3: Technical alarm
Sensor-3 activation results in a
*9713
61
##
*
Value
#
Value
Info
1
Alarm if contact closes or signal is applied
(
Factory setting
)
3
Alarm if contact opens or signal cease to apply
28
Alarm due to Sensor-3
2 activated
NO
NC
NO
NC
NO
OFF
OFF
NC
NO
OFF
OFF
NC
2 deactivated