Wattstopper

 

®

Ultrasonic Low Voltage Occupancy Sensor with Manual On Feature (v3)
Détecteur de présence à ultrasons basse tension avec marche en mode manuel (v3)
Sensor de ocupación ultrasónico de bajo voltaje con función de encendido manual (v3)

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24254 – 10/16  rev. 1

Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: UT-305-1, UT-305-2, UT-305-3

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

SPECIFICATIONS

Voltage  ................................18-28VDC/VAC, half wave rectified AC
Current Consumption ...............................................................25mA
Power Supply ...........................................Wattstopper Power Packs
Operating Temperature .............................32° to 131°F (0° to 55°C)
Time Delay Adjustment ............................30 seconds to 30 minutes
 

Walk-Through Mode ..........3 minutes if no activity after 30 sec.

 

Test Mode .................................... 5 sec. upon DIP switch reset

Ultrasonic Coverage

 

Model UT-305-1 ..................................................... up to 500 ft

2

 

Model UT-305-2 ................................................... up to 1000 ft

2

 

Model UT-305-3 ................................................... up to 2000 ft

2

 

Sensitivity Adjustment ............. Minimum to Maximum (trimpot)

 Frequency .......................................................................40kHz

UL & CUL Listed for use with Wattstopper Power Packs

U.S. Patents: 7,277,012

DESCRIPTION AND OPERATION

The Wattstopper UT-305 sensors turn lighting systems on and off 

based on occupancy. 
The UT-305 can be configured to turn lighting on, and hold it on as 

long as it detects cccupancy. After no movement is detected for a user 

specified time (5 to 30 minutes) the lights are switched off. A “walk-

through” mode can turn lights off after only 3 minutes, if no activity is 

detected after 30 seconds of an occupancy detection.
The UT-305 operates on 24V supplied by Wattstopper Power Packs. 

The sensors can operate on 24VDC, 24VAC, or half wave rectified AC.

COVERAGE PATTERN

The UT-305 is available in 3 models. Each model has a different size 

coverage pattern. The coverage shown represents walking motion at a 

mounting height of 8 to 10 feet. For building spaces with lower levels of 

activity or with obstacles and barriers, coverage size may decrease.

0'

5'

12'

16'

23'

0'

5'

16'

23'

45'

12'

12'

16'

23'

12' 16' 23'

45'

UT-300/305-3

UT-300/305-2

UT-300/305-1

UT-300/305-3

HALLWAY 

APPLICATION

Drawings not to scale.

PLACEMENT GUIDELINES

Depending upon obstacles such as furniture or partitions, the area 

of coverage may be less or more than the sensing distances shown 

in the coverage pattern. This must be considered when planning the 

number of sensors and their placement. It is also recommended to 

place the sensor 4 to 6 feet away from air supply ducts.

Mount the sensor to the ceiling.

 The UT-305 is designed for a 

ceiling height of about 8-10 feet. Mounting above or below this range 

will significantly affect the coverage patterns. As a general rule, each 

occupant should be able to clearly view the sensor.

Open Office Area Coverage:

 To get complete coverage in an open 

office area, install multiple sensors so that there is approximately 

20% overlap with each adjacent sensor’s ultrasonic coverage area.

2QH87

&RYHUDJH$UHD

8OWUDVRQLF

2YHUODS

Summary of Contents for Wattstopper UT-305-1

Page 1: ...utes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The UT 305 operates on 24V supplied...

Page 2: ...ower pack to the 24V terminal on the sensor BLACK wire Return from power pack to Common terminal on the sensor BLUE wire from power pack to Control Out terminal on sensor To add a manual switch such a...

Page 3: ...ings can be done using the following procedures To make adjustments open the Front Cover with a small screwdriver Before making adjustments make sure the office furniture is installed lighting circuit...

Page 4: ...he load stays OFF For the selected time delay the lights stay OFF and the sensor reverts to the automatic on mode When the load is turned OFF manually pressing the switch again turns the load ON and t...

Page 5: ...Voltage with Manual On Feature UT 305 2 Ultrasonic Occupancy Sensor up to 1000 sq ft coverage Low Voltage with Manual On Feature UT 305 3 Ultrasonic Occupancy Sensor up to 2000 sq ft coverage Low Vol...

Page 6: ...n courant alternatif redress mono alternance PORT E Le d tecteur UT 305 est disponible en 3 mod les Chaque mod le poss de un sch ma de port e de taille diff rente La port e indiqu e dans le sch ma rep...

Page 7: ...c d alimentation Noir Rouge 1 2 Interrupteurs tension de ligne Bo tier arri re Borne d branchable Plafond Clips ressort 2 C blage standard avec interrupteur d arr t local C blage de la marche manuelle...

Page 8: ...vous que les meubles de la zone de travail sont install s que les circuits d clairage sont allum s et que les syst mes CVCA sont en position neutralis marche Les syst mes DAV doivent tre r gl s sur le...

Page 9: ...tion du r glage de la logique de pr sence La temporisation du d tecteur s applique comme programm Lorsque la charge se COUPE en raison d une absence de d tection de pr sence elle peut tre ACTIV E de n...

Page 10: ...rcharge est pr sente Une fois ce probl me corrig le d tecteur reprend son fonctionnement normal Solutions possibles 1 R duisez la sensibilit des ultrasons dans le sens inverse des aiguilles d une mont...

Page 11: ...funcionar con 24 V CC 24 V CA o CA de media onda rectificada PATR N DE COBERTURA El sensor UT 305 est disponible en 3 modelos Cada modelo tiene un patr n de cobertura de un tama o diferente La cobert...

Page 12: ...5 Azul Salida de control 24V Com n Bajo voltaje Clase 2 Voltaje de l nea L nea Neutro Alimentaci n directa Fuente de Energia Negro Rojo 1 2 Interruptores de voltaje de l nea Alojamiento trasero Cubier...

Page 13: ...encendidos y de que los sistemas de climatizaci n est n en la posici n de anulaci n encendido Los sistemas VAV deben configurarse con su m ximo caudal de aire Configure el tiempo de retardo en el val...

Page 14: ...rruptor 2 Si se activa el interruptor manual mientras la carga est encendida esto apaga la carga Cuando se apaga la carga manualmente siempre y cuando el sensor siga detectando la presencia la carga s...

Page 15: ...n mero 1 arriba Ajuste del sensor para el reajuste del sensor 4 Configure la sensibilidad y el retardo de tiempo al m nimo y permita que el sensor agote el tiempo de espera Si las luces se apagan el...

Page 16: ...directos con respecto a la p rdida de propiedad renta o ganancias o al costo de extracci n instalaci n o reinstalaci n WARRANTY INFORMATION INFORMATIONS RELATIVES LA GARANTIE INFORMACI N DE LA GARANT...

Reviews: