background image

3

MOUNTING THE SENSOR

Directly to Ceiling

1.  Attach the plastic spring clips to the edge of the sensor in the slots provided.
2.  Cut a 3.5” to 4” round hole in the acoustic ceiling tile at the mounting location. A 3.5” hole 

is recommended for a secure fit.

3.  Pull the low voltage wire from the power pack to the sensor through the hole.
4.  Connect the low voltage wires to the appropriate terminals on the sensor.
5.  Push the sensor up through the hole until the Spring Clips hold the sensor securely in 

place.

6.  Snap the front cover onto the sensor.

Using an Octagonal J-Box

1.  Pull the low voltage wires from the power pack into the J-Box through the conduit 

knockout.

2.  Connect the low voltage wires to the appropriate terminals on the sensor.
3.  Loosen the appliance mounting screws attached to the J-Box
4.  Align the sensor in the J-Box so that the mounting screws on the box match the key 

holes on the sensor’s rear housing.

5.  Push the sensor up into the J -Box and twist it so that the mounting screws are seated in 

the keyhole slots.

6.  Tighten the two screws to secure the sensor to the J-Box.
7.  Snap the front cover onto the sensor.

'HSOXJJDEOHWHUPLQDO

5HDU

+RXVLQJ

2FWDJRQDO-%R[

DWOHDVWGHHS

)URQW

&RYHU

&HLOLQJ

6FUHZV

J-Box Mount

SENSOR ADJUSTMENT

NOTE: This unit is pre-set for basic operation as described in this guide. Adjustment is optional. 

The sensors are factory preset to allow for quick installation in most applications. 

Verification of proper wiring or coverage, or customizing the sensor’s settings can 

be done using the following procedures. To make adjustments, open the Front 

Cover with a small screwdriver.
Before making adjustments, make sure the office furniture is installed, lighting 

circuits are turned on, and the HVAC systems are in the overridden/ on position. 

VAV systems should be set to their highest airflow. Set the Time Delay to the 

desired settings. See 

DIP Switch Setting

.

To Test Occupancy Sensors

1.  Ensure the Time Delay is set for 

Test Mode*

 using the “Test Mode/20 

minutes” setting. (DIP Switches 1, 2, & 3 are 

OFF

). 

2.  Ensure that the Ultrasonic Sensitivity trimpot is set to about 70%, clockwise.

3.  Remain still. The LED should not flash. The lights should turn off after 5 

seconds. (If not, see 

Troubleshooting

.)

4.  Move about the coverage area. The lights should come 

ON

. Adjust the Ultrasonic Sensitivity as necessary to provide the desired 

coverage (Green LED indicates activation from the ultrasonic sensor).

When testing and adjustment are complete, reset DIP Switches to the desired settings, and replace the cover on the sensor.
*Test Mode is a temporary state that starts when you first set the sensor’s DIP Switches for the “Test Mode/20 minutes” (Switches 1, 2, 

OFF

). If you need to invoke the Test Mode and the DIP Switches are already set for Test Mode/20 minutes, toggle DIP Switch 1 

ON

then back to the 

OFF

 position. This provides a 10 minute test period. During the test period, the Time Delay is only 5 seconds.

.H\KROHVORWV

IRUPRXQWLQJWR

RFWDJRQDOER[

'RXEOHJDQJ

PXGULQJ

PRXQWLQJKROHV

',3VZLWFKHV

21

(&(

8OWUDVRQLF

WUDQVGXFHU

FRQHV

8OWUDVRQLF

DFWLYLW\

/('*UHHQ

/LJKWOHYHO

SXVKEXWWRQ

8OWUDVRQLF

VHQVLWLYLW\WULPSRW

Rear

housing

Depluggable terminal

Front

cover

Ceiling

Spring clips (2)

Ceiling Mount

Summary of Contents for Wattstopper UT-305-1

Page 1: ...utes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The UT 305 operates on 24V supplied...

Page 2: ...ower pack to the 24V terminal on the sensor BLACK wire Return from power pack to Common terminal on the sensor BLUE wire from power pack to Control Out terminal on sensor To add a manual switch such a...

Page 3: ...ings can be done using the following procedures To make adjustments open the Front Cover with a small screwdriver Before making adjustments make sure the office furniture is installed lighting circuit...

Page 4: ...he load stays OFF For the selected time delay the lights stay OFF and the sensor reverts to the automatic on mode When the load is turned OFF manually pressing the switch again turns the load ON and t...

Page 5: ...Voltage with Manual On Feature UT 305 2 Ultrasonic Occupancy Sensor up to 1000 sq ft coverage Low Voltage with Manual On Feature UT 305 3 Ultrasonic Occupancy Sensor up to 2000 sq ft coverage Low Vol...

Page 6: ...n courant alternatif redress mono alternance PORT E Le d tecteur UT 305 est disponible en 3 mod les Chaque mod le poss de un sch ma de port e de taille diff rente La port e indiqu e dans le sch ma rep...

Page 7: ...c d alimentation Noir Rouge 1 2 Interrupteurs tension de ligne Bo tier arri re Borne d branchable Plafond Clips ressort 2 C blage standard avec interrupteur d arr t local C blage de la marche manuelle...

Page 8: ...vous que les meubles de la zone de travail sont install s que les circuits d clairage sont allum s et que les syst mes CVCA sont en position neutralis marche Les syst mes DAV doivent tre r gl s sur le...

Page 9: ...tion du r glage de la logique de pr sence La temporisation du d tecteur s applique comme programm Lorsque la charge se COUPE en raison d une absence de d tection de pr sence elle peut tre ACTIV E de n...

Page 10: ...rcharge est pr sente Une fois ce probl me corrig le d tecteur reprend son fonctionnement normal Solutions possibles 1 R duisez la sensibilit des ultrasons dans le sens inverse des aiguilles d une mont...

Page 11: ...funcionar con 24 V CC 24 V CA o CA de media onda rectificada PATR N DE COBERTURA El sensor UT 305 est disponible en 3 modelos Cada modelo tiene un patr n de cobertura de un tama o diferente La cobert...

Page 12: ...5 Azul Salida de control 24V Com n Bajo voltaje Clase 2 Voltaje de l nea L nea Neutro Alimentaci n directa Fuente de Energia Negro Rojo 1 2 Interruptores de voltaje de l nea Alojamiento trasero Cubier...

Page 13: ...encendidos y de que los sistemas de climatizaci n est n en la posici n de anulaci n encendido Los sistemas VAV deben configurarse con su m ximo caudal de aire Configure el tiempo de retardo en el val...

Page 14: ...rruptor 2 Si se activa el interruptor manual mientras la carga est encendida esto apaga la carga Cuando se apaga la carga manualmente siempre y cuando el sensor siga detectando la presencia la carga s...

Page 15: ...n mero 1 arriba Ajuste del sensor para el reajuste del sensor 4 Configure la sensibilidad y el retardo de tiempo al m nimo y permita que el sensor agote el tiempo de espera Si las luces se apagan el...

Page 16: ...directos con respecto a la p rdida de propiedad renta o ganancias o al costo de extracci n instalaci n o reinstalaci n WARRANTY INFORMATION INFORMATIONS RELATIVES LA GARANTIE INFORMACI N DE LA GARANT...

Reviews: