11
Press
Select
L M L S - 5 0 0 0 2 9 3 7 2 4 9 0 9
Z o n e S e t u p
C a l i b r a t i o n
Z o n e S e t t i n g s
A d v a n c e d S e t t i n g s
C o n t r o l M o d e
Choose
Calibration
L i g h t s w i l l w a r m u p
a n d r e m a i n O N f o r
t w o m i n u t e s
P l e a s e w a i t 1 2 0 s e c .
Counts down from120 seconds
then returns to the Main Menu
Enter light level for
ALL zones
C a l i b r a t i n g L M L S - 5 0 0
P o i n t t o A n y I R
e n a b l e d d e v i c e o n
t h e n e t w o r k
P r e s s ‘ S e l e c t ’
Point and
Press Select
Ta k e a l i g h t l e v e l
a t Z o n e 1
Z o n e 1 : 5 0 f c
N E X T
C a l i b r a t i n g L M L S - 5 0 0
( F u l l O n )
C a l i b r a t i n g L M L S - 5 0 0
( F u l l O n )
Ta k e a l i g h t l e v e l
a t Z o n e 1
Z o n e 3 : 5 0 f c
N E X T
Press
Select
Choose
NEXT
Calibration (LMLS-600 Only)
The role of the calibration process is to establish, for the
controlled zone, the appropriate setpoint for operation, to learn
the dimming curves of the controlled loads, and to create an
initial daylight ratio for closed-loop versus open-loop sensors.
This can be done Automatically or Manually.
Automatic Calibration
Automatic Calibration can be started by the LMCT-100, a similar
menu in LMCS, or by pressing and holding the user pushbutton
(located on the bottom of the sensor, farthest from the RJ45
connection) for three seconds.
S e n s o r C o n fi g u r a t i o n
L o a d C o n fi g ( P n L )
D a y l i g h t i n g C o n fi g
B u t t o n C o n fi g u r a t i o n
D i m m i n g C o n fi g u r a t i o n
M o r e
=
B AT
Press
Select
Press
Select
L M L S - 6 0 0 0 2 9 3 6 1 1 9 3 5
Z o n e S e t u p
C a l i b r a t i o n
Z o n e S e t t i n g s
A d v a n c e d S e t t i n g s
C o n t r o l M o d e
Choose
Calibration
D a y l i g h t i n g L M L S - 6 0 0
A u t o m a t i c C a l i b r a t i o n
M a n u a l C a l i b r a t i o n
Main Menu
P l e a s e l e a v e t h e a r e a
a n d r e t u r n a f t e r t h e
B l u e L E D s t o p s
b l i n k i n g
P r e s s ‘ S e l e c t ’ t o
c o n t i n u e o r ‘ H o m e ’ t o
c a n c e l A u t o C a l i b r a t e
C a l i b r a t i n g L M L S - 6 0 0
NOTE:
It is critical that, during the Automatic Calibration
process, the area under the sensor, as well as the
skylight area, remain free of any obstructions, and that
no changes occur (including human foot traffic) within
the cone-of-view of the closed loop sensor. Please clear
the area before starting the Automatic Calibration, and
wait for the calibration completion (when the blue LED
stops flashing once every 4 seconds) before reentering
the area.
D a y l i g h t i n g C o n fi g
( L M L S - 4 0 0 )
N i g h t S e t u p
N i g h t S e t p o i n t S a v e d
Press
Up/Down
arrow
Increment (raise)
Decrement (lower)
D a y l i g h t i n g C o n fi g
( L M L S - 4 0 0 )
N i g h t S e t u p
U s e t h e U p / D o w n K e y s
t o s e t t h e d e s i r e d
D a y l i g h t l e v e l
D a y l i g h t i n g C o n fi g
( L M L S - 4 0 0 )
I n c r e m e n t i n g t h e
L i g h t l e v e l
N i g h t S e t u p
Continue adjusting pressing the
Up or Down arrow until
desired Light Level is achieved
D a y l i g h t i n g C o n fi g
( L M L S - 4 0 0 )
W h e n d o n e a d j u s t i n g
p r e s s S e l e c t
N i g h t S e t u p
Press
Select
When Day and Night adjustments are complete, press the HOME
key to terminate Manual Calibration and return to normal operation.
Calibration (LMLS-500 Only)
Calibration allows you to establish a relationship between
the workplane luminance and the measured daylight at the
photocell.
Light Level at Photocell
0
20
40
60
80
100
0
500
1000
1500
2000
1750
70
Li
ght
Le
ve
l at
Task
Use the LMCT-100-2 for the Calibration process.
1. Complete all wiring and turn power ON to the connected
room controllers.
2. Select the LMLS-500 to be calibrated using the LMCT-100.
3. Select Calibration. For each Zone, choose a reference
location that is most likely to have the lowest light level
when day lit for each zone.
4. With the electric lights ON, use a light meter to measure
the light level in each zone.
5. Enter the measured light level at the task surface per zone,
in the LMCT-100.
6. Daylighting controlled loads will turn OFF.
7. Use a light meter to measure the light level in each zone.
8. Enter the measured light level at the task surface per zone
in the LMCT-100.
9. Select the Send button to establish communication with
the LMLS-500.