MESSAGES DISPLAYED ON START-UP
MESSAGE
MEANING AND OPERATING TIPS
WARNING:
alarm records in memory!
It is necessary to confirm the turning on of the EPS in presence of alarms in the
even list
WARNING: different UPS setup!
The EPS configuration has changed from the last power up. A skilled technican
must check the setup before confirming the power up.
Maintenance Bypass!
Open output
Open the output breaker before turning on the EPS to exit the manual mainte-
nance bypass mode.
Turn ON after low battery turn OFF.
The EPS is turned on after a previous end of autonomy
<ENTER> to confirm UPS turn ON
Press the ENTER key to turn on the EPS
CRITICAL EVENTS (paragraph 6.4.4)
MESSAGE
MEANING AND OPERATING TIPS
Inverter Fail
Fault detected in the Inverter circuit. One or more power modules are faulty. A
skilled technician must replace them.
Booster Fail
Fault detected in the Booster/PFC circuit. One or more power modules are
faulty. A skilled technician must replace them.
Battery Charger Fail
Fault detected in the Battery charger circuit. One or more power modules are
faulty. A skilled technician must replace them.
Overheat
Overheating. Check the ventilation system.
Overload
Overload. Check the connected load level.
H.V.Bus Runaway Failure
Contact the LEGRAND Technical Support Service
Output DC Level
A skilled technician must check that there is not a faulty power module or a
voltage backfeed from the output
Battery voltage too high
Excessive battery voltage. A skilled technician must check the batteries.
Power Module comm. failure
Contact the LEGRAND Technical Support Service
Emergency
Contact the LEGRAND Technical Support Service
Load turned OFF
The output load power has been cut off
Irregular TurnOff
EPS shutdown in an anomalous way. The skilled technician must make sure
that there is no voltage inside the equipment before performing any mainte-
nance operation.
Overload TurnOff
EPS shutdown due to an extended overload
Emergency Power Off turn-OFF
EPS shutdown due to an Emergency Power Off
Battery KO
Fault in the batteries. A skilled technician must check them.
Power Module battery wiring
failure
There is a fault in the connection of the batteries to the power modules. One or
more power modules are faulty. A skilled technician must replace them.
Power Module mains wiring failure
There is a fault in the connection of the mains to the power modules. One or
more power modules are faulty. A skilled technician must replace them.
continue...
Summary of Contents for Trimod MCS 10
Page 1: ...Item LE10960AA 01 19 01 CT Trimod MCS User manual ...
Page 2: ...2 UK ENGLISH 3 Trimod MCS ...
Page 16: ...16 3 3 Models Trimod MCS 3 5 10 Trimod MCS 7 15 3 Technological description ...
Page 17: ...Trimod MCS User manual 17 Trimod MCS 30 Trimod MCS 20 ...
Page 18: ...18 Trimod MCS 40 Trimod MCS 60 Trimod MCS 80 3 Technological description ...
Page 58: ...58 ...
Page 59: ...Trimod MCS User manual 59 ...