Trimod MCS
U
ser manual
43
7.2
Messages
This paragraph shows the messages that appear on the control panel display or in the event list (see paragraph 6.4.4) and
the probable cause that could have generated them.
INDICATION
If it is not possible to solve the problem, contact the LEGRAND Technical Support Service.
FIRST ROW OF THE MAIN SCREEN
MESSAGE
MEANING AND OPERATING TIPS
TRIMOD MCS
The EPS is operating properly
Service mode
EPS in Service Mode. The parameters can be modified through the control
panel and updates can be made.
UPS initialize...
The EPS is starting-up
CM initialize...
The command board is starting-up all the associated power modules after the
exit from the hot-swap mode.
CM turning off...
The command board is turning off all the associated power modules after
entering the hot-swap mode
Service Mode...
The EPS is starting up in Service Mode.
Maintenance Bypass
The load is powered directly from the mains by means of the manual bypass.
Forced on Bypass
The EPS has entered the forced Bypass mode through a selection from the
control panel.
UPS on Bypass
EPS in bypass mode.
Bypass line KO
A skilled technician must check the bypass line.
EPS in stand-by
Output non powered during normal functioning (with mains present)
Modules turned OFF
Command board in hot-swap.
The power modules are no longer powered and ready to be replaced.
Output/phase turned OFF
Phase or Output off. Configuration obtained via display or after a EPS
malfunctioning.
UPS on battery
EPS in battery mode. A fault in the equipment power supply system or a loss of
mains has occurred.
UPS in off-line
The load is powered directly from the bypass line. In case of a power failure,
the equipment switches to battery mode.
Battery Cal...
The EPS is performing the calibration of the batteries through a command
from the control panel.
Battery Test...
The EPS is carrying out a test on the batteries in order to check their status and
proper operation.
Equalizing Battery
The EPS is performing battery equalization.
Buzzer Muted
The buzzer has been silenced.
RUNTIME RESERVE!
The battery charge is low while the EPS is working in battery mode.
FAULT MODULE
One or more power modules are faulty. A skilled technician must replace them.
continue...
Summary of Contents for Trimod MCS 10
Page 1: ...Item LE10960AA 01 19 01 CT Trimod MCS User manual ...
Page 2: ...2 UK ENGLISH 3 Trimod MCS ...
Page 16: ...16 3 3 Models Trimod MCS 3 5 10 Trimod MCS 7 15 3 Technological description ...
Page 17: ...Trimod MCS User manual 17 Trimod MCS 30 Trimod MCS 20 ...
Page 18: ...18 Trimod MCS 40 Trimod MCS 60 Trimod MCS 80 3 Technological description ...
Page 58: ...58 ...
Page 59: ...Trimod MCS User manual 59 ...