22
4.4
Movement
WARNING
Move the EPS very carefully, lifting it as little as possible and avoiding dangerous swings or falls.
The equipment must always be handled by trained and instructed personnel equipped with the Personal Protective
Equipment illustrated in chapter 2.
The EPS has wheels at the back of the cabinet. Before installations, and while it is still empty, it can be moved by hand by
at least two people.
For any lifting, use a forklift or a transpallet with an adequate carrying capacity, placing the forks in the wooden base and
making sure they come out the other side by at least twenty centimetres.
WARNING
Do not move the equipment after installation or following the insertion of power modules and any battery drawers.
4.5
Positioning constraints
The EPS must be positioned respecting the following condi-
tions:
- temperature and humidity must be within permitted limits;
- fire regulations must be respected;
- the wiring must be simply made;
- front and rear accessibility must be available for assistance or
periodic servicing;
- the cooling flow of air must be guaranteed;
- the air conditioning system must be adequately scaled;
- dust or corrosive/explosive gasses must be absent;
- the premises must be free of vibration;
- the rear and side space must be enough to guarantee an ade-
quate circulation of air for cooling;
- the support surface must be scaled in for the carrying capacity
necessary to support the equipment.
To safeguard the batteries as well as possible it is necessary to bear in mind that their average lifetime is strongly influ-
enced by the operating room temperature.
Position the equipment in an environment with a temperature range b20°C (+68°F) and +25°C (+77°F) to guar-
antee the optimum life of the batteries.
Before proceding with the installation operations, make sure that there is enough lighting to clearly see every detail.
Provide artificial lighting if the natural lighting does not satisfy the requirements cited.
In the case of maintenance operations in places that are not sufficiently well lit, portable lighting systems must be used.
4.6
Final operations
Once the EPS has been properly positioned, fit the two base strips and the
front one provided in the accessory kit.
Minimum
recommended
distances for the EPS
X=100 mm /
Y=200 mm
Minimum
recommended
distances Trimod
MCS UPS + Trimod
MCS BATTERY
X=100 mm /
Y=200 mm
MCS
BATTERY
CABINET
MCS
4. Unpacking and positioning
Summary of Contents for Trimod MCS 10
Page 1: ...Item LE10960AA 01 19 01 CT Trimod MCS User manual ...
Page 2: ...2 UK ENGLISH 3 Trimod MCS ...
Page 16: ...16 3 3 Models Trimod MCS 3 5 10 Trimod MCS 7 15 3 Technological description ...
Page 17: ...Trimod MCS User manual 17 Trimod MCS 30 Trimod MCS 20 ...
Page 18: ...18 Trimod MCS 40 Trimod MCS 60 Trimod MCS 80 3 Technological description ...
Page 58: ...58 ...
Page 59: ...Trimod MCS User manual 59 ...