UNIT DESCRIPTION AND OPERATION

The OSR300S is a passive infrared wall switch that turns lighting on and off
based on occupancy and ambient light levels. SmartSet™ technology allows the
sensor to be installed without any adjustments and automatically adjusts it to
the usage patterns in the space. Alternate operating modes, selected by DIP
switch settings, can be combined to create the ideal custom control.
The OSR300S contains two relays. Dual buttons on the front of the OSR300S
allow the user to control one or two loads independently. Pressing an ON/OFF
button toggles the state of the corresponding relay, turning the load on if it is
currently off, or off if it is currently on. If no motion is detected during the time
delay that is in effect, the load will turn off.
The OSR300S also contains a light level sensor that, when enabled, operates
on the secondary relay. If adequate daylight is present, the sensor holds the
secondary load off until light levels drop, even when the controlled area is
occupied. Users can override this function by blocking the light coming into the
sensor by placing their hand over the sensor lens until the load comes on. The
load will then remain on until the space is unoccupied.

Turning The Load On

The relays are programmed independently for either Auto On or Manual On.
In either mode, the load can be turned on or off using the ON/OFF button.

Auto On

Load turns on and off automatically based on occupancy.

If the load is turned off manually, automatic-on is reenabled

when no motion is detected for five minutes. This prevents the

load from being turned on after it was deliberately turned off.

Manual On

Occupants must turn on the load by pressing the ON/OFF but-

ton. The sensor keeps the load on until no motion is detected

for the selected time delay. There is a 30 second reset delay. If

motion is detected during this time, the sensor turns the load

back on automatically. After the reset delay time has elapsed,

the ON/OFF button must be pressed to turn on the load.

Time Delays

The OSR300S holds the load on until no motion is detected for the selected
time delay. You select either SmartSet or a Fixed time delay using DIP switch
settings. The sensor automatically sets the time delay when SmartSet is
enabled; with the fixed time delay settings you select a time delay between
5 to 30 minutes, and whether the Walk-Through mode is included.
Both relays use the same delay, unless a delayed disconnect is enabled for relay
2 using the Delay Relay 2 Disconnect feature. This delayed disconnect feature is
useful in applications where you want both loads to turn off automatically, but
want relay 2 to stay on longer, such as when running an exhaust fan after the
lights have shut off.

Call 800.223.4185 for Technical Support

Summary of Contents for Pass & Seymour OSR300S

Page 1: ...Horsepower Rating each relay 1 6 HP Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 15 sec upon initial power up or DIP switch reset PIR Sensit...

Page 2: ...ither Auto On or Manual On In either mode the load can be turned on or off using the ON OFF button Auto On Load turns on and off automatically based on occupancy If the load is turned off manually aut...

Page 3: ...cancels automatically after five minutes or if a fixed time delay is selected To reenable the Test Mode for an additional five minutes change the time delay from any fixed amount to the SmartSet Test...

Page 4: ...wing Fresnel lens with 180 degree field of view Masking the lens Opaque adhesive tape is supplied so that sections of the sensor s view can be masked This allows you to eliminate coverage in unwanted...

Page 5: ...n Wait one minute then push the Auto ON OFF switch for each load and the lights will turn on There is a delay due to initial power up of the sensor that only occurs during installation Screw Terminal...

Page 6: ...N OFF 6 Auto On Manual On Relay 2 ON Mode 4 Use Relay 1 Delay Add 10 minutes Delay Relay 2 Disconnect 1 2 3 4 5 6 7 8 Time Delay FACTORY PRESETS Delay Relay 2 Disconnect ON Relay 1 On Mode Relay 2 On...

Page 7: ...follow the directions below All major adjustments to the OSR300S must be made with the wall plate removed To access the DIP switches remove the button cap by squeezing the top sides of the button asse...

Page 8: ...eturn or repair 2 return the product to Pass Seymour Legrand postage paid with your name and address and a written description of the installation or use of the Pass Seymour Legrand product and the ob...

Reviews: