39
KEOR S 3-10 kVA
Oper
ating & I
nstalla
tion M
anual
The front panel located at the front side of the UPS, informs the user about operating status, alarm condi-
tions and measurements. It also provides access to control and configuration parameters.
The cable connections, the circuit breakers and the communication slots are located at the Rear Panel.
8.1.
Front Panel Segments
Front panel shown below consists of two segments. LCD (Liquid Crystal Display) offers detailed information
about UPS and KEYPAD enables the user to access the UPS.
8.1.1.
Keypad
Figure.8.1.1-1
Figure.8.1.1-2
Front View
Keor S 3kVA
Front Panel
8. Front Panel & Rear Panel
NO
Front Panel Item Definition
1
LCD Display
2
UPS Fault LED
3
Amber LED lights up to indicate the Bypass Input is normal. It lights up and lights off when UPS operates in Eco Mode.
4
It indicates that UPS output is OK.
5
Green LED steadily lights up to indicate that the Utility input voltage is within the window (160Vac~288Vac); the LED
flashes flickeringly to indicate that the Utility input voltage is within the acceptable window (120Vac~159Vac)
6
UPS On/Alarm Silence
7
UPS OFF Switch
8
Special functions log in/out
9
Go to next page
10
Go to previous page or change the setting of the UPS
11
To re-confirm the change of UPS Setting
Table10