3.3.
Important Notice for UPS
• The equipment may only be installed and commissioned by authorized LEGRAND UPS Technical Service Personnel.
• This manual contains important instructions that you should follow during installation and maintenance of the
UPS and batteries. Please read all instructions before installing the equipment and save this manual for future
reference.
• Not obeying the instructions written on this manual which may result with possible injury of the operator or
damage of the equipment.
• The equipment shall be packed properly during transportation and proper equipment should be used for
transportation. Never transport in horizontal position.
• The UPS must always stands in a vertical position. Make sure that the floor can support the weight of the system.
• Connect the PE ground connector before connecting any other cable.
• Because of “LITTLE LEAKAGE CURRENTS” generated by EMI Filter of the UPS, it is necessary to double ensure if the
earth of the UPS is properly grounded before AC mains is connected with.
• UPS is designed for indoor use. To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled indoor environment, free of conductive contaminants. Ambient temperature must not exceed
40°C (104°F). Do not operate near water or excessive humidity (95% maximum without condensation).
• UPS requires 1Ph-N+PE input connection.
• Neutral system: refer to Section 5.3.1.5 Output Connection.
• Even when connections removed, residual voltages of capacitors and/or high temperature may exist on
connection terminals and inside the UPS. Before working on terminals, check between all the terminals included
PE that no hazardous voltages exist.
• The connections shall be made with cables of appropriate cross-section in order to prevent the risk of fire. All
cables shall be of insulated type and shall not be laid out on the walking path of the persons.
• According to IEC 62040-2; this is a category C2 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
• Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or
UPS.
• Make sure that the UPS is not overloaded to provide a higher quality supply to the loads.
• In case of an extraordinary situation (damaged body, cabinet or connections, penetration of foreign materials
into the body or cabinet etc.) de-energize the UPS immediately and consult to the LEGRAND Technical Assistance
Center.
• When used for particular applications such as life support systems or any other application where product failure
is likely to cause substantial harms to person, we would advise you to contact LEGRAND UPS to confirm the ability
of these products to meet the requested level of safety, performance, reliability and compliance with applicable
laws, regulations and specifications.
The following indications summarize the protective gear to wear.
Accident and spark proof footwear with rubber sole and reinforced toe
Use : always
Waterproof rubber gloves
Use : always
Protective gear
Use : always
Protective glasses
Use : always