Installation and start-up of KEOR HPE UPS 200 kVA
Installazione e avviamento KEOR HPE UPS 200 kVA
OMP06144 REV. A
41
Picture 12 – Inverter start-up
3)
As the inverter is correctly started-up, close the bypass switch SBCB when indicated by
the display. The logic will check the correctness of the bypass phase sequence and
RMS voltage value.
Picture 13 – Bypass start-up
4)
Close the battery switch BCB when indicated by the display.