Installation and start-up of KEOR HPE UPS 200 kVA
Installazione e avviamento KEOR HPE UPS 200 kVA
44
OMP06144 REV. A
5.5
RESTART FROM MANUAL BYPASS
Before restarting the UPS from manual by-pass, make sure the “Bypass_Sw" selector is in
BYPASS
position and the MBCB isolator is closed.
1)
Close the rectifier input switch RCB. After some seconds the
touch screen
will start and
will show the UPS mimic diagram.
Picture 17 – Start-up from manual bypass
2)
After the software loading phase the control logic will acquire the system status and the
operation of the RCB switch, and will show the operating sequences. Close the switch
SBCB as requested.
Picture 18 – Bypass start-up