INSTALLATION INSTRUCTIONS
F-2189
• Applications Metrex Egress METEL Series
wall surface mount unit equipment for high
abuse environments. See fixture label
for restrictions.
Features
• Sealed, maintenance-free nickel-cadmium
battery. Standard fixture is suitable for use in
10°C (50°F) to 45°C (113°F) environments.
CEL option includes a thermostatically
controlled battery warmer and is suitable
for use in -30°C (-22°F) to 45°C (113°F)
environments. Follow Kenall Instruction Sheet
F-2929 for proper wiring of unit.
• Self-testing circuitry automatically conditions
the battery and performs regularly scheduled
tests that conform to NFPA 101Life Safety
Code. Self-diagnostic circuitry monitors
battery, charger, power transfer and lamp
functions.
Installation (Figs. 2, 3)
• Follow Kenall Instruction Sheet F-2932 for
proper mounting,assembly and wiring of unit.
Start Up (Figs. 2, 3)
• Do not apply power to fixture unless supply
can be maintained for at least 7 days without
interruption.
• If battery is not connected when power is
applied, the selfdiagnostic feature will detect
the missing battery and the status LED will
display a steady red signal. Connect the
battery and reset the system by pressing
and holding the manual test pushbutton for
approximately 7 seconds.
• Battery connection sequence: Always connect
BATTERY CONNECTOR 1 first and BATTERY
CONNECTOR 2 (if equipped) second. Always
disconnect in reverse order.