CANOPY MOUNTING (Figs. 1, 2, 4): Remove front
SHIELD and STENCIL ASSEMBLY.
Remove ELECTRICAL CHASSIS by disengaging tabs
in upper corners. Remove REFLECTOR
(if provided). Locate appropriate HOUSING drill
points and drill (2) 5/16” dia. holes for
MOUNTING CANOPY attachment and (1) hole of
suitable size for supply wire entry. Place
MOUNTING PLATE over an installed electrical
junction box (slotted holes provided for
temporary j-box attachment prior to permanent
mounting). Locate and drill 4 pilot holes in
mounting surface using MOUNTING PLATE as a
template. For wet location installation, attach
self-adhesive pad GASKET to MOUNTING PLATE.
Using 1/4-20 fasteners and anchors
appropriate for the mounting surface (not supplied),
attach MOUNTING PLATE to structure.
Connect supply ground to GROUND WIRE provided.
For wet location installation, attach selfadhesive
pad GASKET to CANOPY COVER. Using HARDWARE
provided, attach CANOPY
COVER and HOUSING to CANOPY
MOUNTING PLATE.
ALL MOUNTING TYPES (Fig. 1, 3, 4) Configure
DIRECTIONAL ARROWs as needed. To
remove DIRECTIONAL ARROW COVER, use 7/16”
nut driver (not supplied) to loosen
RETAINER NUT approx. one complete turn and push
in cover from outside. Tighten RETAINER
NUT to secure COLOR FILTER PANEL and aluminum
LIGHT MASK (if provided). Install
ELECTRICAL CHASSIS. Install REFLECTOR (if
provided), routing supply wires thru center hole
(if wall mounted). Route supply wires around
ELECTRICAL CHASSIS and connect to
appropriate push-in connectors. Connector lead
color coding: White= Neutral, Black= 120V,
Orange= 277V, Blue= 347V. Install front STENCIL
ASSEMBLY and SHIELD to HOUSING using
Posigrip fasteners (included) and 9500 screwdriver
(ordered separately).
CONDUIT ATTACHMENT(Fig. 5) ½” trade size
conduit may be used for power entry into top or
end of HOUSING or into center of REAR PANEL.
Locate suitable drill point and drill 7/8” dia.
hole. HOUSING is reversible for conduit entry
from either end (Note UP indicator). Use proper
conduit hub and locknut for wet or damp/dry
location installation (not supplied).
Applications
Millenium Metrex METDU, METDW,
MWESW series
Features
• Sealed, maintenance-free nickel-cadmium
battery. EL option is suitable for use in
10ºC to 40°C environments. EL-CW option
includes a thermostatically controlled battery
warmer and is suitable for use in -40°C to
40°C environments.
• Self-testing circuitry automactically conditions
the battery and performs regularly scheduled
tests that conform to NFPA 101 Life Safty
Code. Self-diagnostic circuitry monitors
battery, charger, power transfer and lamp
functions.
Installation
• Fixture is shipped with battery
disconnected.
• Follow Kenall Installation Instruction Sheet
F-2189 FOR proper mounting, assembly and
wiring of unit.
• After installing electrical chassis and making
field wiring connections ( AC power OFF),
connect polarized 2-pin battery connector to
PC board assembly.
• Exit legend will illuminate for a few seconds
and then extinguish. This signals that battery
is properly connected and is protected from
discharging until AC power is established.
• Attach front stencil assembly and shield.