background image

www.kenall.com  |  P: 800-4-Kenall  |  F: 262-891-9701  |  10200 55th Street Kenosha, Wisconsin 53144, USA         

This product complies with the Buy American Act: manufactured in the United State swith more than 50% of the component cost of US origin It may be covered by patents 
found at www.kenall.com/patents. Content of specification sheets is subject to change; please consult www.kenall.com for current product details. ©2019 Kenall Mfg.Co. 

2

INSTALLATION INSTRUCTIONS

F-2189

INSTALLATION (cont’d)

CANOPY MOUNTING (Figs. 1, 2, 4): Remove front 
SHIELD and STENCIL ASSEMBLY.
Remove ELECTRICAL CHASSIS by disengaging tabs 
in upper corners. Remove REFLECTOR
(if provided). Locate appropriate HOUSING drill 
points and drill (2) 5/16” dia. holes for
MOUNTING CANOPY attachment and (1) hole of 
suitable size for supply wire entry. Place
MOUNTING PLATE over an installed electrical 
junction box (slotted holes provided for
temporary j-box attachment prior to permanent 
mounting). Locate and drill 4 pilot holes in
mounting surface using MOUNTING PLATE as a 
template. For wet location installation, attach
self-adhesive pad GASKET to MOUNTING PLATE. 
Using 1/4-20 fasteners and anchors
appropriate for the mounting surface (not supplied), 
attach MOUNTING PLATE to structure.
Connect supply ground to GROUND WIRE provided. 
For wet location installation, attach selfadhesive
pad GASKET to CANOPY COVER. Using HARDWARE 
provided, attach CANOPY
COVER and HOUSING to CANOPY 
MOUNTING PLATE.

ALL MOUNTING TYPES (Fig. 1, 3, 4) Configure 
DIRECTIONAL ARROWs as needed. To
remove DIRECTIONAL ARROW COVER, use 7/16” 
nut driver (not supplied) to loosen
RETAINER NUT approx. one complete turn and push 
in cover from outside. Tighten RETAINER
NUT to secure COLOR FILTER PANEL and aluminum 
LIGHT MASK (if provided). Install
ELECTRICAL CHASSIS. Install REFLECTOR (if 
provided), routing supply wires thru center hole
(if wall mounted). Route supply wires around 
ELECTRICAL CHASSIS and connect to
appropriate push-in connectors. Connector lead 
color coding: White= Neutral, Black= 120V,
Orange= 277V, Blue= 347V. Install front STENCIL 
ASSEMBLY and SHIELD to HOUSING using
Posigrip fasteners (included) and 9500 screwdriver 
(ordered separately).
   

CONDUIT ATTACHMENT(Fig. 5) ½” trade size 
conduit may be used for power entry into top or
end of HOUSING or into center of REAR PANEL. 
Locate suitable drill point and drill 7/8” dia.
hole. HOUSING is reversible for conduit entry 
from either end (Note UP indicator). Use proper
conduit hub and locknut for wet or damp/dry 
location installation (not supplied).
Applications

Millenium Metrex METDU, METDW, 

MWESW series

Features
•   Sealed, maintenance-free nickel-cadmium 

battery. EL option is suitable for use in 

10ºC  to 40°C environments. EL-CW option 

includes a thermostatically controlled battery 

warmer and is suitable for use in -40°C to 

40°C environments.

 

•   Self-testing circuitry automactically conditions 

the battery and performs regularly scheduled 

tests that conform to NFPA 101 Life Safty 

Code. Self-diagnostic circuitry monitors 

battery, charger, power transfer and lamp 

functions.

Installation
•   Fixture is shipped with battery 

disconnected.

 

•   Follow Kenall Installation Instruction Sheet 

F-2189 FOR proper mounting, assembly and 

wiring of unit. 

•   After installing electrical chassis and making 

field wiring connections ( AC power OFF), 

connect polarized 2-pin battery connector to 

PC board assembly. 

•   Exit legend will illuminate for a few seconds 

and then extinguish. This signals that battery 

is properly connected and is protected from 

discharging until AC power is established.

•   Attach front stencil assembly and shield. 