56
PRODUCT SELECTION (CONTINUED)
One power supply module can
provide up to 500 mA, so
consumption must be calculated
in order for the installation to work
correctly.
CX³ EMS modules power consumption
CAT.NO
DESCRIPTION
MAXIMUM
CONSUMPTION
4 149 18
Single-phase measurement module with 3 digital inputs up to 63 A
34.8 mA
4 149 19
Single-phase measurement module with digital input up to 63 A
34.1 mA
4 149 20
Three-phase measurement module with digital input up to 63 A
34.8 mA
4 149 21
Three-phase measurement module with 3 digital inputs up to 125 A
34.8 mA
4 149 22
Three-phase measurement open flexible Coil 630 A 1MOD
34.8 mA
4 149 23
High current measurement module
32.6 mA
4 149 24
Three-phase measurement open flexible Coil 1600 A 1MOD
34.8 mA
4 149 25
Three-phase measurement open flexible Coil 3200 A 1MOD
34.8 mA
4 149 26
Pulse concentrator module
24.0 mA
4 149 27
Three-phase measurement open flexible Coil 6300 A 1MOD
34.8 mA
4 149 29
AC + FS module (Aux fault signalling contact)
19.7 mA
Black cable 4 149 01/02/03
Connector
4 149 10
Connector
White cable
Black cable
Black cable
Connector
The white cable provided with the power supply module is 250 mm
long. If a longer cable is needed, an extension can be created using
“conventional” (black) CX³ EMS cables and extension connectors.
Maximum length of assembly: 3 m.
Summary of Contents for EMS CX3
Page 6: ...4 CX3 EMS complete compact and multifunctional MEASUREMENT SIGNALLING...
Page 33: ...31 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM...
Page 39: ...37 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM...
Page 47: ...45 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM...
Page 65: ...63 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM...
Page 69: ...67 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM...
Page 75: ...73 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM...
Page 95: ...93 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM Notes...
Page 96: ...94 Notes...
Page 97: ...95 TECHNICAL GUIDE CX EMS Energy Management System WWW LEGRAND COM Notes...