Description of “Voltage control line 2 S.Q2” menu
M07 – VOLTAGE CONTROL LINE 2 S.Q2
UDM
DEFAULT
RANGE
P07.01
MIN voltage limit for trip
%
85
70-100
P07.02
MIN voltage restore
%
90
70-100
P07.03
MIN voltage delay
s
5
0-600
P07.04
MAX voltage limit for trip
%
115
100-130 / OFF
P07.05
MAX voltage restore
%
110
100-130 / OFF
P07.06
MAX voltage delay
s
5
0-600
P07.07
Return of power in the limits delayed
(when S.Q1 source not available)
s
10
1-6000
P07.08
Return of power in the limits delayed
(when S.Q1 source available)
s
60
1-6000
P07.09
Phase failure threshold
%
70
60 - 80
OFF
P07.10
Phase failure delay
s
0.1
0.1s-30s
P07.11
MAX Asymmetry limit
%
15
1 -20
OFF
P07.12
MAX Asymmetry delay
s
5
0.1-900
P07.13
MAX frequency limit
%
105
100-120
OFF
P07.14
MAX frequency delay
s
3
0-600
P07.15
MIN frequency limit
%
95
OFF
80-100
P07.16
MIN frequency delay
s
5
0-600
P07.17
S.Q2 control OFF mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P07.18
S.Q2 control MAN mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P07.19
Time delay generator starter due to a
lack of S.Q2
s
OFF
OFF / 1-6000
P07.20
Generator cooling time
s
120
1-3600
Note: For details on the functions of parameters see the menu M06 – “voltage control S.Q1 (line 1)”.