LEGRAND 0 3 100 51 Installation Manual Download Page 20

Daker DK 1, 2, 3 kVA

41

EN

8 Technical features

CONSTRUCTION SPECIFICATIONS

3 100 50

3 100 51

3 100 52

Weights

16 Kg

29,5 Kg

30 Kg

Dimensions L x H x P in mm

440 x 88 x 405 440 x 88 x 650 440 x 88 x 650

Protection

Electronic protection against overloading 

and short-circuiting. Shutdown on reaching 

operating limit and overheating.

Automatic shutdown due to protection 

triggering

Ambient specifications

Operating temperature range

from 0 to +40 °C

Operating relative humidity range

from 20 to 80% non-condensing

Degree of protection as per IEC529

IP20

Noise level at 1 meter

< 50 dBA

Electrical input specifications

Rated input voltage

230 V

Range of input voltage

from 160 V to 288 V

Rated input frequency

50 or 60 Hz ± 5Hz

Maximum input current

5,2 Arms

10,4 Arms

15 Arms

Number of input phases

Single phase

Waveform on output

With battery operation

sinusoidal

Type of operation

on line - double conversion

Electrical specifications on output

Rated output voltage

230 V ± 1%

Active output capacity on nominal load

800W

1,6 kW

2,4 kW

Apparent output capacity on nominal load

1kVA

2 KWA

3 KWA

Overload capacity

105% continuous

120% for 30 seconds

150% for 10 seconds

Number of phases on output

Single phase

Summary of Contents for 0 3 100 51

Page 1: ... Part LE05334AC 07 13 01 GF Daker DK 1 2 3 kVA Manuel d installation Installation manual ...

Page 2: ... 1 2 3 kVA Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator self diagnostic software 37 6 Battery replacement 38 7 Possible malfunctioning 40 8 Technical features 41 ...

Page 3: ... be parts inside with dangerously high voltage even when the mains plug is disconnected there are no parts inside that the user can repair The front control panel is provided for manual operations Do not press on the panel with sharp or pointed objects The UPS Daker DK has been designed to work in closed clean rooms where there are no inflam mable liquids or corrosive substances and where it is no...

Page 4: ...mmable Outlets 1 and 2 are present 5 The orange LED indicates that the Bypass is active 6 UPS alarm LED 7 UPS power on buzzer silencing pushbutton 8 UPS power off pushbutton 9 Special functions access menu pushbutton log in out 10 Following screen selection pushbutton 11 Previous screen selection or settings change pushbutton 12 Selection confirmation pushbutton 2 3 4 5 6 7 8 9 10 11 12 1 ...

Page 5: ...Service Mode operation 7 UPS off 8 UPS alarm 9 UPS operation diagram 10 Measurements display 11 It indicates which parameter is being measured 22 Battery insufficient or needing replacing 23 Short circuit on the output 24 Excessive inverter current 25 Overtemperature 26 Overload on the output 27 Other Alarms LINE OFF FAIL Er05 Er06 Er10 Er11 Er12 Er ...

Page 6: ...y Input circuit breaker 22 Cooling Fans 23 Output circuit breaker for two outlets 24 Output circuit breaker for two programmable outlets INTERFACE INPUT BREAKER AC INPUT AC OUTPUT 1 2 DC 72V G G EPO A B 1 2 OUTPUT BREAKER 1 2 AC OUTPUT EPO DC 36V AC INPUT INPUT BREAKER INTERFACE G G 13 14 15 16 17 18 19 20 21 22 INTERFACE INPUT BREAKER AC INPUT AC OUTPUT 1 2 DC 72V G G EPO 3 100 50 13 14 15 16 17 ...

Page 7: ...S with IEC sockets only detached AC Input Power cable for UPS with IEC sockets only RS 232 communication cable USB communication cable Tower Rack Accessories Kit as below A1 A2 Optional A4 A3 Optional B2 B1 4 pcs 1 pcs 1 pcs 1 pcs 2 pcs 2 pcs S1 2 pcs M3 6 0 1 0mm S2 8 pcs M3 6 0 1 0mm S3 6 pcs M4 8 0 1 0mm ...

Page 8: ...Daker DK 1 2 3 kVA 29 EN Tower configuration setup A1 A1 A1 A1 A3 A2 Step 1 Step 2 ...

Page 9: ...30 4 Installation UPS battery cabinet optional A4 Step 1 Step 2 ...

Page 10: ...Daker DK 1 2 3 kVA 31 EN B2 B1 S3 90 Step 1 Step 2 Step 3 Step 4 ...

Page 11: ...32 4 Installation Step 5 Step 6 ...

Page 12: ...ct the input connector 18 the power cable and the output cables to the appropriate connectors 19 3 Connect the loads to the output cables ensuring that the switches of the various users are off 4 Connect the power supply plug to a power socket with suitable voltage and current Start 1 Switch on the power breaker 21 of the distribution panel Then the UPS will start up Green LEDs and and show that t...

Page 13: ... for the more critical loads To access both this and other functions download the UPS Setting tool free of charge from the www ups legrand com website UPS Default Data and Special Function Execution 1 After the UPS is turned on successfully press the Special Functions button to change the LCD to figure P1 P1 P2 2 Press the key to scroll through the UPS settings The LCD will display in sequence fig...

Page 14: ...Daker DK 1 2 3 kVA 35 EN R1 R2 S T U1 U2 U3 V ...

Page 15: ... up key 4 Figures R1 and R2 indicate the bypass input acceptable window It can be 180 260 VAC for 220 VAC systems 90 130 VAC for 110 VAC systems 194 260 VAC for 220 VAC systems or 97 130 VAC for 110 VAC systems 5 Figure S indicates the bypass frequency window of the inverter output The acceptable settings are 3 Hz and 1 Hz 6 Figure T indicates the acceptable Inverter OutputVoltage Possible values ...

Page 16: ...face sockets indicate the reference number that can be found on the back of the UPS using an RS232 or USB cable 5 UPS communicator self diagnostic software From the website www ups legrand com it is possible to download free of charge a self diagnostic software running on WINDOWS 16 e 32 bit e Linux platforms This software can be used for the following functions Display of all the operation and di...

Page 17: ...38 6 Battery replacement Step 1 Step 2 ...

Page 18: ...Daker DK 1 2 3 kVA 39 EN Step 3 Step 4 3 100 50 Step 4 3 100 51 3 100 52 ...

Page 19: ... shuts down or immediately signals it is close to the operating limit The UPS has operated with no mains voltage for a long time and has not been able to recharge the battery Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery is flat due to not using the UPS for a long period Recharge it for at least 6 hours by connecting the uninterruptible po...

Page 20: ...ndensing Degree of protection as per IEC529 IP20 Noise level at 1 meter 50 dBA Electrical input specifications Rated input voltage 230 V Range of input voltage from 160 V to 288 V Rated input frequency 50 or 60 Hz 5Hz Maximum input current 5 2 Arms 10 4 Arms 15 Arms Number of input phases Single phase Waveform on output With battery operation sinusoidal Type of operation on line double conversion ...

Page 21: ...time 10 min 10 min 8 min Charging time 4 6 hours at 80 of the charge Technical data and number of batteries n 3 maintenance free sealed lead battery 12V 7 2Ah n 6 maintenance free sealed lead battery 12V 7 2Ah n 6 maintenance free sealed lead acid battery 12V 9Ah Standards Electromagnetic compatibility Emission Immunity Conforms to EN 62040 2 Safety Conforms to EN 62040 1 Performance and features ...

Reviews: