CS-D508 Closed-loop Stepper Drive User Manual
Motion Control Products Ltd. Tel.: (+44) 01202 599922
GND
A+
A-
+Vdc
Encoder Signal
Connector
1
5
6
Power &
Motor Connector
Controller
Black
Red
Control Signal
Connector
4
PUL+
DIR+
PUL-
DIR-
ENA+
ENA-
5V
Step
Direction
Enable
EA+: BLK EA-: BLU
EB+: YEL EB-: GRN
+5V: RED GND: WHT
Fault
5-24V
ALM+
1
2
ALM-
Status Signal
Connector
24-48VDC recommended,
leaving rooms for voltage fluctuation
and back EMF of the motor
2
Encoder
Extension Cable*
Encoder
Cable
*must be used
Power
Extension Cable
Power
Cable
3
B+
B-
Yellow/Green
Blue
CS-D508
Load
Figure 7: Typical connection
8. Sequence Chart of Control Signals
In order to avoid some fault operations and deviations, PUL, DIR and ENA should abide by some rules, shown as following
diagram:
Figure 8: Sequence chart of control signals
Remark:
a)
t1: ENA must be ahead of DIR by at least 500ms. Usually, ENA+ and ENA- are NC (not connected). See
“Connector P1 Configurations” for more information.
b)
t2: DIR must be ahead of PUL effective edge by 5us to ensure correct direction;
c)
t3: Pulse width not less than 2.5us;
d)
t4: Low level width not less than 2.5us.