6
Warning: When you are connecting the wire, please make sure that the input, output wire
and the input, output terminals are connected tightly.
Terminals block:
6. Reinstall the cover and lock the cover with a screwdriver
①
.
7. After connecting the wire and AC, then put the UPS input breaker to "ON", the UPS will be
powered.
2.4 External battery connection of long back up type UPS
The nominal DC voltage of external battery pack is 192VDC. Each battery pack consists of 10
pieces of 12V batteries in series. To achieve longer backup time, its possible to connect
multi-battery packs.
The battery connecting procedure is very important, if you do not follow the procedure, you
may encounter the hazardous of electric shock. So please strictly follow the steps below.
1. Set the battery breaker in "OFF" position and connect suitable battery in series.
2. Selecting a suitable battery cable to connect between the battery pack and UPS.(Refer to
table 2.2) One DC breaker must be connected between the battery pack an the UPS, The
capability of breaker must be not less than the data specified in the general.
Model
6KS(L)
10KS(L)
Battery voltage
192VDC
192VDC
Battery current
34A. max
56A.max
Summary of Contents for Dragon Power 2