13
02-2 Battery low voltage shutdown point/End of discharge voltage (EOD)
LCD Display
Setting
The options of EOD setting are dEF, 9.8V, 9.9V, 10V, 10.2V, 10.5V.
By default, the EOD is dEF
(The EOD will be changed according to loading condition.
10.5V@load
<
25%
,
10.2V@25%
<
load
<
50%
,
10V@load
>
50%).
02-3: Economic Operation Mode
LCD Display
Setting
ECO is OFF by default, can be set as ON to improve the efficiency
of system operation.
Note: For the models with PF
<
1, OFF by default, and unable to
set.
02-4: Emergency shutdown (EPO)
LCD Display
Setting
When EP is set to ON, the EPO option appears on the function
setting page. Emergency shutdown can be set as closed or open
to trigger, the default is open to trigger.
Note: After EPO action, emergency shutdown, close all outputs
immediately.