4
Load at high altitude=Rated power *Derating factor (corresponding to altitude)
Altitude(m)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating factor
100%
95%
91%
86%
82%
78%
74%
70%
67%
Notice: If the machine is used at above 1000m, diminishing ratings output must be used,
please refer to above table for derating factor.
1.4 Electromagnetic compatibility
Safety
IEC/EN 62040-1-1
EMI
Conducted Emission
……
IEC/EN 62040-2
Class A
Radiated Emission.........IEC/EN 62040-2
Class A
EMS
ESD.................................IEC/EN 6100-4-2
Level 4
RS...................................IEC/EN 6100-4-3
Level 3
EFT..................................IEC/EN 6100-4-4
Level 4
SURGE............................IEC/EN 6100-4-5
Level 4
Low Frequency Signals
……
IEC/EN 6100-2-2
Warning: This is a product for commercial and industrial application in the second
environment-installation restriction or additional measures may be needed to prevent
disturbances.
NOTICE:
This is a product for restricted sales distribution to informed partners. Installation restrictions
or additional measures may be needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of
0-40
℃
(32-104
℉
). Install it in a clean environment, free from moisture, flammable liquids,
gases and corrosive substance.
This UPS contains no user-serviceable parts except the internal battery pack. The UPS ON/OFF
push buttons do not electrically isolate internal parts. Under no circumstance attempt to gain
access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the panel indications are not accordance with these
operating instructions or the UPS performance alters in use. Reflect all faults to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the precautions.
Keep unauthorized personnel away from the batteries. Proper disposal of batteries is required.
Refer to your local laws and regulations for disposal requirement.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the
UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryer or any appliance
using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn off and isolate the UPS before cleaning it. Use only a dry cloth, never liquid or aerosol
cleaners.