- 17 -
SETTING UP THE ANALOG OUTPUT
Under the Analog Out tab, set Source to Item 3. Under Range, select 0-20 mA, 4-20 mA, 0-10V
or -10V to +10V as your desired analog output. Enter your Lo Range Reading and Hi Range
Reading. These will create the two endpoint values of your analog output range. Only enter the
numerical values. The decimal point is ignored. The span between the two values should be at
least 256 counts to minimize the size of analog output steps.