9. LTS SETUP FOR STREAMING INPUT WITH CUSTOM ASCII PROTOCOL
Set Signal input
to None. Set Time Out to 000.00 Secs if you want the analog output to be held
indefinitely in the absence of a new serial input, or specify another time in seconds. Ignore
Signal Input, Gate Time, Filter and Power-On Total.
Under Display,
select one of the Remote
operating modes shown. Please see the screen captures below for more information.
Remote A
is an addressable input mode for up to 31 LTS units. The received ASCII text strings
must be in a format like
*#KSDDDDDD.A<CR>
*
= Recognition character. Another command recognition character may be chosen to make
the transmitter compatible with an existing system. The transmitter will still respond to
an asterisk.
#
= Device Address Code from 1 to V.
Device #
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Address Code 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V
K
= Command letter. Can be programmed using the Custom ASCII protocol to be H, K or L.
S
= Optional sign of value. Use space or + for positive, - for negative.
D
= Digits from 0 to 9. There can be 1 to 6 digits.
.
= Optional decimal point. Can be anywhere between or after D
D
D
D digits.
A
= Optional Alarm Character which overrides internal comparisons. A = no alarms, B = alarm
1 active, C = alarm 2 active, D = alarms 1 & 2 active.