5.  SAFETY CONSIDERATIONS

 

 

 

 

Warning:

 Use of this transmitter in a manner other than specified may impair the protection 

of the device and subject the user to a hazard. Visually inspect the unit for signs of damage. If the 
unit is damaged, do not attempt to operate. 

Caution:  

 

This  unit  may  be  powered  with  AC  (mains)  from  85-264  Vac  or  90-300  Vdc  with  the  high 
voltage  power  supply  option,  or  12-30  Vac  or  10-48  Vdc  with  the  low  voltage  power  supply 
option.  Verify  that  the  proper  power  option  is  installed  for  the  power  to  be  used.  This 
transmitter has no AC (mains) switch. It will be in operation as soon as power is applied. 

 

The  85-264  Vac  or  90-300  Vdc  mains  connector  (P1  Pins  1-3)  of  model  LTS60  is  colored 

green

 to differentiate it from other input and output connectors. The 12-30 Vac or 10-48 Vdc 

mains connector of model LTS61 is colored 

black

 

The analog output is 

sourcing

. Do not connect the 4-20 mA analog output to a load designed 

to apply 24 Vdc to a two-wire transmitter. Applying 24 Vdc will burn out the main board. 

 

To avoid dangers of electrocution and/or short circuit, do not attempt to open the case while 
the  unit  is  under  power.  However,  signal  wiring  changes  external  to  the  case  can  be  made 
safely while the unit is under power.   

 

To prevent electrical or fire hazard, do not expose the transmitter to excessive moisture. 

 

Do not operate the transmitter in the presence of flammable gases or fumes. Such an environ-
ment constitutes an explosion hazard.  

 

Secure the transmitter to a 35 mm DIN rail. 

 

Symbols used: 

 

Caution (refer to accompanying 
documents)    

 

 

Caution, risk of electric shock.    

 

Equipment protected throughout  
by double insulation or reinforced 
insulation.    

 

Earth (ground) terminal. 

 

Both direct and alternating current. 

 

 

Operating environment: 

 

Class II (double insulated) equipment  
designed for use in Pollution degree 2. 

PROVISION FOR COOLING

PROVISION FOR COOLING

PROVISION FOR COOLING

PROVISION FOR COOLING    

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

 

 

To avoid overheating, mount transmitters 
with ventilation holes at t

op and bottom. 

Leave a minimum of 6 mm 1/4”

) between 

transmitters, or force air with a fan. 

Summary of Contents for LTS

Page 1: ...OR RS485 SERIAL INPUT ANALOG OUTPUT TRANSMITTER Modbus or Custom ASCII Protocol OWNERS MANUAL LAUREL Electronics Inc 3183 G Airway Ave Costa Mesa CA 92626 USA Tel 714 434 6131 Fax 714 434 3766 Website...

Page 2: ...120 mA solid state relays Default jumpered for RS232 LTSE6E Transmitter with 4 20 mA 0 20 mA 0 10V or 10V to 10V isolated analog output Ethernet serial data input and dual 120 mA solid state relays Po...

Page 3: ...5 SAFETY CONSIDERATIONS 6 6 TRANSMITTER FIELD WIRING 7 7 JUMPER SETTINGS 8 8 PROGRAMMING YOUR TRANSMITTER 10 9 LTS STREAMING DATA INPUT MODE WITH CUSTOM ASCII PROTOCOL 12 10 LTS COMMAND MODE WITH CUST...

Page 4: ...l values or to transmitted control characters which override the internal setpoints The relays can also be controlled independently of the serial input by applying signals to control inputs 1 and 2 Is...

Page 5: ...prior to shipment Should the transmitter be damaged in shipment notify the freight carrier immediately In the event the transmitter is not configured as ordered or is inoperable return it to the plac...

Page 6: ...Vdc will burn out the main board To avoid dangers of electrocution and or short circuit do not attempt to open the case while the unit is under power However signal wiring changes external to the case...

Page 7: ...7 6 TRANSMITTER FIELD WIRING...

Page 8: ...place a jumper at E1 cycle power remove the jumper and restart the transmitter Analog Output J4 Pins Jumpers Current 4 20 mA 1 Lo 2 Hi E2 a d Voltage 0 10V 1 Lo 2 Hi E2 b c Voltage 10V to 10V 3 Lo 2...

Page 9: ...ettings are for RS232 input and 4 20 mA output HOW TO OPEN CLOSE THE CASE The two clamshell halves of the case are held together with a bolt and a nut at each of the four corners Use a Phillips screwd...

Page 10: ...ort of the PC CBL02 incorporates and FTDI chip which is compatible with all versions of MS Windows USING INSTRUMENT SETUP IS SOFTWARE As a first step set User Account Control UAC of your version of Wi...

Page 11: ...the next time that you run IS software From the Main Menu click on Counter Get Setup to retrieve or get the existing setup data from your counter transmitter Click on View Setup to bring up screens w...

Page 12: ...haracter Another command recognition character may be chosen to make the transmitter compatible with an existing system The transmitter will still respond to an asterisk Device Address Code from 1 to...

Page 13: ...CR Remote 2 2nd value of value sequence SDDDD DDSDDDD DDSDDDD DDSDDDD DD CR Remote 3 3rd value of value sequence SDDDD DDSDDDD DDSDDDD DDSDDDD DD CR Remote 4 4th value of value sequence SDDDD DDSDDDD...

Page 14: ...ing Control Input 1 Control Input 2 or both Selections applicable to the serial input transmitter are the following Meter Reset Function Reset Meter Reset first row When this row is selected grounding...

Page 15: ...multiple data values and non numeric characters Under this tab you can reselect your Baud Rate Device Address Serial Protocol and Full Half Duplex even though you may have selected different values t...

Page 16: ...ight Under this tab you can reselect Baud Rate Device Address Serial Protocol and Full Half Duplex even though you may have selected different values to es tablish initial communications with your PC...

Page 17: ...V to 10V as your desired analog output Enter your Lo Range Reading and Hi Range Reading These will create the two endpoint values of your analog output range Only enter the numerical values The decima...

Page 18: ...reading is compared if deviation is set to zero The reading is the count in engineering units that is transmitted digitally and is also used for analog output For example if the transmitted reading is...

Page 19: ...s and Band Deviation These define how Setpoint and Deviation are to be combined to set Alarm State Span Hysteresis for heater control Band Deviation for component testing In Split Hysteresis the relay...

Page 20: ...the transmitter s control inputs which has been set to Function Reset under the Input Display tab Alarms 1 2 No Rdgs to Alarm Selections are binary steps from 1 to 128 This is the number of consecutiv...

Page 21: ...to 10V Enter the Lo Range and Hi Range numerical readings which will serve as endpoints for the selected output type Set the LTS Source value to Item 3 which will be used for analog output interpolat...

Page 22: ...section entitled FC03 READ FC10 WRITE HOLDING REGISTER ADDRESSES Use Hi Word starting Register Addresses and an even number of Registers The Register Addresses shown in this section apply to both FC0...

Page 23: ...t in a directory of your choice Create a desktop icon from the installed executable Before using qModMaster ensure that your LTSE transmitter has been set to Modbus RTU as explained in the Instrument...

Page 24: ...how Tx and Rx values written correctly For information on these values please see our Modbus Manual for Counters at https www laurels com downloadfiles Modbus Manual CTR pdf The screen captures below...

Page 25: ...rst Alarm1 is forced by writing 01 01 01 01 to holding register 0x006 This turns Relay1 on Then Alarm2 is forced by writing 03 03 03 03 to holding register 0x006 This turns Relay2 on Both relays are t...

Page 26: ...26...

Page 27: ...at 9600 baud Dual Relay Outputs standard Relay Type Two solid state relays SPST normally open Form A Load rating 120 mA at 140 Vac or 180 Vdc Relay modes Active high or low latching or non latching hy...

Page 28: ...ns 5 Mishandling or abuse The warranty set forth above is exclusive and no other warranty whether written or oral is expressed or implied Laurel specifically disclaims implied warranties of merchantab...

Reviews: