Installation
GL16
2-6
NOTE:
Exceeding a 45° elbow
angle rotation from vertical for the
blower may not maintain proper air
movement and may cause the
sail switch to operate incorrectly.
Installing the Exhaust Blower
1.
Position the 10" (254 mm) exhaust blower
in the opening in the center of the canopy.
Secure the blower in place with the four
machine screws provided.
2.
Extend the 10" (254 mm) round exhaust
ducting from the exhaust blower output
to the outside discharge point.
The discharge must be properly designed to
maintain the required air flow:
•
To ensure proper operation of the exhaust
canopy sail switch and the correct removal
of by-products, it is recommended that the
unit be connected to a separate exhaust
system.
•
The discharge must be protected from
backdrafts and precipitation.
•
No screen or filter should be connected
at the discharge unless it is connected to
a commercial lint collector.
Exhaust Blower Installation
The exhaust canopy includes a blower to expel
excess heated air and moisture. This system
contributes to the comfort of operating personnel,
proper operation of the unit, and reduction of
maintenance time. All labor and materials
required for venting the unit are a local
responsibility. Comply with local codes and
regulations for proper installation.
Ductwork
The 10" (254 mm) diameter ductwork and all
associated hardware for the exhaust system must
be locally supplied. Follow local codes and good
engineering practice to design the exhaust system.
Every effort should be made to keep the ductwork
as short and straight as possible. Check the
canopy nameplate for the maximum length of
ductwork. Do not use elbows greater than a 45°
angle in the exhaust ducting.
Locating the Exhaust Blower
NOTE:
Proper installation is
required for all warranties and
applicable certification labels to be
valid. Call the factory if you have
any questions.
The exhaust blower is designed for vertical
installation directly on top of the exhaust canopy
(Figure 2-10). It is particularly important that a
straight section of ductwork be attached directly
to the blower discharge. When it is installed, the
blower can be rotated up to a 45° angle to the left
or right of vertical to help make this configuration.
CAUTION
Do not change the mounting
position of the sail switch
and do not reverse the
blower housing.
Required Tools
slotted screwdriver
Figure 2-10: The exhaust blower assembly is
mounted on top of the canopy.
Summary of Contents for Flatwork Ironer Series
Page 1: ...GL16 Gas Heated Flatwork Ironer INSTRUCTION MANUAL...
Page 8: ...Skyline S1 S20 Installation...
Page 12: ......
Page 18: ...Skyline S1 S20 Installation...
Page 58: ...Skyline S1 S20 Installation...
Page 76: ...Skyline S1 S20 Installation...
Page 94: ...Skyline S1 S20 Installation...
Page 166: ...Skyline S1 S20 Installation...
Page 168: ......
Page 176: ...8 PL 3031 009c GL16 Drive Side View Type R Only...
Page 183: ...15 GL16 PL 3031 009c This Page Blank on Purpose...
Page 186: ...18 PL 3031 009c GL16 Disconnect Panel...
Page 188: ......
Page 189: ...GL16 Schematics and Parts 3210 361...
Page 190: ...2...
Page 192: ...4...
Page 194: ...6...
Page 196: ...8...
Page 198: ...10...
Page 200: ...12...
Page 202: ...14...
Page 203: ...GL16 15...
Page 204: ...Skyline S1 S20 Installation...
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 214: ......
Page 216: ......
Page 217: ...3045 001a...
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 238: ......