Func
Code
Name
Range
Min
Unit
Factory
Default
Modify
PA.07
Motor rotor inductance 0.1
5000.0mH
~
0.1mH
depends on
model type
×
PA.08
Motor stator and rotor
mutual inductance
0.1
5000.0mH
~
0.1mH
depends on
model type
×
PA.09
Motor stator
resistance
0.001
50.000
Ω
~
0.001
Ω
depends on
model type
×
PA.10
Motor rotor resistance
0.001
50.000
Ω
~
0.001
Ω
depends on
model type
×
PA.11
Over current
protection coefficient
of torque current
0
15
~
1
15
×
PA.12
Proportion adjustment
coefficient of speed
deviation
50
120
~
1
85
×
PA.13
Integral adjustment
coefficient F speed
deviation
100
500
~
1
360
×
PA.14
Vector torque boost
100
150
~
1
100
×
PA.15
Reserved
0
0
0
×
PA.16
Reserved
1
5
~
1
4
×
PA.17
Reserved
100
150
~
1
150
×
PA.18
Reserved
150
1
150
×
PA.19
Reserved
0
2
~
1
0
×
PF Group: Factory function parameter
PF.00
~
PF.10
Reserved
---
---
---
---
B-Monitoring: function parameter
b-00
Output freq
Present output freq
0.01Hz
----
*
b-01
Set freq.
Present set freq.
0.01Hz
----
*
b-02
Output voltage
Effective value of
present output voltage
1V
----
*
b-03
Output current
Effective value of
present output current
0.1A
----
*
b-04
Bus bar voltage
Present DC bus bar
voltage
1V
----
*