Func
Code
Name
Range
Min
Unit
Factory
Default
Modify
P4.10
2-way open
collector output
terminal OC1
output
selection
0 VFD in running(RUN)
1 Freq. arrival signal(FAR)
2 Freq. level detected signal(FDT1)
3 Reserved
4 Overload pre-alarm signal(OL)
5 Under voltage locking(LU)
6 External fault stopping (EXT)
7 Output freq. upper limit(FH)
8 Output freq. lower limit(FL)
9 VFD in zero speed running
10 Simple PLC stage running finish
11 A PLC running cycle finish
12 Set counts arrival
13 Specified counts arrival
14 VFD ready for running(RDY)
15 VFD fault
16 Start freq. running time
17 DC brake time when start
18 DC brake time when stop
19 Swing freq. upper/lower limit
20 Set running time arrival
21 Upper limit of pressure alarm
signal
22 Lower pressure alarm signal
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
1
0
×
P4.11
2-way open
collector output
terminal OC2
output
selection
Ditto
1
0
×
P4.12
Relay
TA/TB/TC
output
selection
Ditto
1
15
×
P4.13
Relay
RA/RB/RC
output
selection
Ditto
1
0
×
P4.14
Freq. arrival
detection range
0.00
400.00Hz
~
0.01Hz
5.00Hz
×
P4.15
FDT1(freq.
level)
0.00
Upper limit freq
~
0.01Hz 10.00Hz
×