Func
Code
Name
Range
Min
Unit
Factory
Default
Modify
P3
.
00
Freq. control
channel
combination
9: RS485 given
-
CI
-
control
panel
▲
、
▼
key given
10: RS485 given
+
CI
+
External
pulse given
11: RS485 given
-
CI
-
External
pulse given
12: RS485 given
+
VI
+
External
pulse given
13: RS485 given
-
VI
-
External
pulse given
14: VI
+
CI
+
control panel
▲
、
▼
key given
+
digital given (P0.02)
15: VI
+
CI
-
control panel
▲
、
▼
key given
+
digital given (P0.02)
16: MAX
(
VI
,
CI
)
17: MIN
(
VI
,
CI
)
18: MAX
(
VI
,
CI
,
PULSE
)
19: MIN
(
VI
,
CI
,
PULSE
)
20: VI
,
CI(Availability except 0,VI
prior)
21: VI+ Terminal UP/DOWN
22: CI+ Terminal UP/DOWN
1
0
×
P3
.
01
Parameter
initialization
setting
LED unit’s digit:
0: All parameters are allowed to be
modified.
1: All parameters are not allowed
to be
modified except this
parameter itself.
2: All parameters are not allowed
to be
modified except P0.02
parameter and
this parameter
itself
LED ten’s digit:
0: Inaction
1: Factory default reset
2: Clear history fault record
1
0
×
P3
.
02
Parameter
copy
0: Inaction
1: Parameter upload
2: Parameter download
Note: only valid in remote control
mode
1
0
×
Larson Electronics, LLC
Phone:
Fax: (903) 498-3364
www.larsonelectronics.com
21
of
52
VFD-1P-220.240-1HP-7A-DCM