Func
Code
Name
Range
Min
Unit
Factory
Default
Modify
P0
.
06
Max output
freq.
50.00Hz
~
500.00Hz
0.01HZ
50.00HZ
×
P0
.
07
Basic running
freq
1.00Hz
~
500.00Hz
0.01HZ
50.00HZ
×
P0
.
08
Max output
voltage
1
~
480V
1V
VFD
rated
voltage
×
P0
.
09
Torque boost
0.0%
~
30.0%
0.1%
2.0%
×
P0
.
10
Torque boost
cut-off freq.
0.00Hz
~
Basic running freq.P0.07
0.00
50.00Hz
○
P0
.
11
Torque boost
mode
0: Manual
1: Auto
1
0
○
P0
.
12
Carrier freq
1.0K
~
14.0K
0.1K
8.0K
×
P0
.
13
Acc/Dec
mode
selection
0: Linear Acc/Dec
1: Curve Acc/Dec
1
0
×
P0
.
14
Time of S
curve start
stage
10.0
%
~
50.0
%
(
Acc/Dec time
)
P0.14
+
P0.15
《
90
%
0.1%
20.0%
○
P0
.
15
Time of S
curve ascent
stage
10.0
%
~
80.0
%
(
Acc/Dec time
)
P0.14
+
P0.15
《
90
%
0.1%
60.0%
○
P0
.
16
Acc/Dec time
unit
0: Second
1: Minute
0
0
×
P0
.
17
Acc time 1
0.1
~
6000.0
0.1
20.0
○
P0
.
18
Dec time 1
0.1
~
6000.0
0.1
20.0
○
P0
.
19
Upper limit
freq.
Lower limit freq.
~
Max output
freq.P0.06
0.01Hz
50.00Hz
×
P0
.
20
Lower limit
freq.
0.00Hz
~
Upper limit freq.
0.01Hz
0.00Hz
×
P0
.
21
Lower limit
freq.
Running mode
0: Running at lower limit freq
1: Stopping
1
0
×
P0
.
22
V/F curve
setting
0: Constant torque curve
1: Reduced torque curve 1 (1.2
times the power)
2: Reduced torque curve 2 (1.7
times the power)
3: Reduced torque curve 3 (2.0
times the power)
4: Customized V/F curve
1
0
×