INSTALLATION

CIRC

U

IT 

B

REA

K

ER INSTALLATION

Make sure that the equipment is suitable for the installation by comparing nameplate ratings with system requirements.

Inspect the equipment for completeness and check for any damage.

WARNING:

 

MAKE SURE POWER IS TURNED 

OFF

 BEFORE STARTING THE 

INSTALLATION OR PERFORMING ANY MAINTENANCE.

 

 

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION

1. Before mounting the circuit breaker in an electrical system, make sure there is no voltage present

where work is to be performed.

2. Mount no closer to enclosure metal or live parts than is indicated in drawing.

3. All enclosure closing hardware must be installed.

FAILURE TO FOLLOW THESE INSTRUCTONS WILL RESULT IN DEATH OR SEVERE INJURY.

<Table.1> 

Size of Enclosure / 

Tamaño del cierre / 

Taille du boîtier

Dimensions / Dimensiones / Dimensions: inch / pulg / inch(mm)

Metal or Live Electrical Parts / Partes eléctricos metales o 

vivos /Métal ou pièces électriques sous tension

<Fig. 1> 

Clearances for Circuit Breaker / Espacio libre para el interruptor / Dégagements pour disjoncteur

<Fig. 2> 

Circuit Breaker Mounting

Bolt Drilling Plan /

Plan de perforación de 

tornillo de montaje del 

interruptor/ Plan de forage 

des Vis de montage du 

Disjoncteur

<Fig. 3> 

Circuit Breaker

Escutcheon 

Dimensions / 

Dimensiones del escudo 

del interruptor /

Dimensions d’écusson 

du Disjoncteur

W

H

D

W

1.1.89

89 ((448)8)

1.

1.06

06

(2

(27)

7)

#6-32

#6-32 UNC 

UNC

T

ap (2 

ap (2 Holes)

Holes)

4.4.33

33

[1

110

]0]

4.4.33

33

[1

110]0]

0.

0.98

98

 [2 

[25]

5]

0.

0.49

49

[12

[12.5]

.5]

[2

[2P]

P]

[3

[3P]

P]

#6-32

#6-32 UNC 

UNC

T

ap (2 

ap (2 Holes)

Holes)

80% and 100% RATED inch / pulg / po (mm)

W

H

D

a

b

c

Circuit

Breaker

Type

UTE100 

2P, 3P

17.3

(439.4)

8.27

(210)

3.94

(100)

2.58

(65.4)

6.03

(153.1)

3.29

(83.5)

Dimensions for electrical and mechanical clearance to metal or live electrical parts.

(See Fig. 1) To mount the circuit breaker perform the following steps:

1. For individual surface mounting, drill and tap mounting bolts holes according to the drilling plan shown in Fig. 2.

For dead- front cover applications, cut out cover to correct escutcheon dimensions refer to Fig. 3 .

2. If circuit breaker includes factory-or field-installed internal accessories, make sure that accessory wiring can be reached when the

circuit breaker is mounted.

3. Position circuit breaker on mounting surface.

4. Install circuit breaker mounting screws and washers. Tighten hardware securely, but do not exceed 13.3 pound-inches (1.5N.m.)

MPD-XX-CB-SF-489

 Series

 

Summary of Contents for MPD CB-SF-489 Series

Page 1: ...NG CODES RISK OF FIRE OR ELECTRIC SHOCK FIXTURE INSTALLATION REQUIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFO...

Page 2: ...eaker Mounting Bolt Drilling Plan Plan de perforaci n de tornillo de montaje del interruptor Plan de forage des Vis de montage du Disjoncteur Fig 3 Circuit Breaker Escutcheon Dimensions Dimensiones de...

Page 3: ...ion indicates a TRIP position and is between the ON and OFF positions See Fig 4 Circuit Breaker Reset After an automatic or accessory initiated trip or a manual PUSH TO TRIP operation the circuit brea...

Page 4: ...ngth Secci n sin alslamiento Longuer de denudage Size Tama o Calibre Number per Lug Cantidad por zapata Nombre par cosse Conductor Conductor Conducteur Type Tipo Type Ampere Range Gama en A Gamme A Ca...

Page 5: ...them B 3 Arrange wire through wire opening in auxiliary cover to avoid pinching wires 4 Replace auxiliary cover C and be careful not to pinch wires when installing cover Replace all auxiliary cover s...

Page 6: ...rical personnel 3 Turn off all power supplying this equipment before working on or inside equipment 4 Always use a properly rated voltage sensing device to confirm power is off 5 Replace all devices d...

Page 7: ...ding to rated current and function as follows Rated current In A FTU TU MCS UTE100 3P 100 UTE100 2P 100 Type of trip units Tipo de unidad de disparo Type de d clencheurs FTU Fixed thermal Fixed magnet...

Page 8: ...Type of trip units Tipo de unidad de disparo Type de d clencheurs 100A 40 C 2P Im 1000A 100A 40 C 3P Im 1000A 00 1 A 40 C 3P Im 1000A FMU Adjustable thermal Fixed magnetic T rmico ajustable magn tico...

Page 9: ...nside equipment 2 Remove circuit breaker in reverse order of installation TROUBLESHOOTING If problems occur during installation refer to the following guide If trouble persists contact Larson Electron...

Page 10: ...perate if the housing is cracked or damaged All fasteners should be properly seated USE AND CARE Unauthorized modification may impair the function and or safety of this device and could affect the lif...

Reviews: