3-25
Termination - Fixed Breakers
M12 / Equivalent BS bolts to be used for links termination
Tightening torque: 3.2 kgfm
Flat Termination
400A-1600A N08/H/V Fr.3-4P (100% N)
Horizontal Termination
(Bus Coupler Application Only)
400A-4000A N08/H/V Fr.3-4P(100% N)
(Adaptor-CL60968OOOO)
M10 bolts to be used for links termination
Tightening torque: 3.0 kgfm
Holes (on both sides) for Earthing
connections by M10 / Equivalent BS bolt
M 10
19
63
82
6
9
3
0
1
0
8
.8
6
9
1
5
Bolt length for mounting
link(s) on Flat Terminals
to be cumulative link(s)
thickness + 15 mm.
Bolt length
9
4
1
15
5
6
5
6
10
100
100
100
100
100
100
100
73.5
1
2
2
1
0
5
847
3
0
32
3
0
65
100
100
100
100
100
100
100
27
19
Ø
12.9
100
100
100
100
100
100
65
Summary of Contents for U-POWER Omega UW-MTX 1.5G
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ......
Page 8: ......
Page 10: ......
Page 12: ...Microswitch...
Page 15: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 27: ......
Page 30: ...3 12 X X 100 150 mm X 100 150 mm X X 15 max...
Page 45: ...3 27 Termination Draw out Breakers THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 46: ...Termination Draw out Breakers 3 28 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 71: ...3 53...
Page 83: ...4 1 4 1 Cradle Mounted Accessories...
Page 84: ...4 2...
Page 85: ...4 3...
Page 86: ...4 4...
Page 87: ...4 5...
Page 88: ...4 6...
Page 89: ...4 7...
Page 90: ...4 8 4 2 Breaker Mounted Accessories...
Page 92: ...4 10...
Page 93: ...4 11...
Page 94: ...4 12...
Page 95: ...4 13...
Page 97: ...Section 5 Protection Control units 5 1 Identification 5 2 Protection Characteristics...
Page 104: ...5 7 Protection Characteristics Overload I T for UW MTX1 0 2 0 1 1 10 100 1000 10000 10s...
Page 119: ...6 3 6 3 Testing Control circuit Interlocks if breaker is equipped with accessories...
Page 134: ......
Page 136: ...7 7...
Page 142: ...Section 8 Useful Hints...