8-1
Useful Hints
Smart Racking Shutter is open
g out
close
“OFF” button is locke
to reset position
Smart Racking Shutter does not
re-close automatically after
racking handle is pulled out
Smart Racking Shutter does not open
Door open/missing: hence
Door Racking Interlock(26) is
active
Breaker is in-between
Connected/Test/Disconnected
position. Position Indicator
is not aligned with any of
the positions
Close the Smart Racking Shutter (Insert
Racking Handle once & pull back)
the breaker
donot match
eaker
Clear/provide door;
else press Door Racking Interlock
lever (on extreme lower lef
“OFF” button not k
Rack-in or out the
breaker to any of the
distinct positions
ACB cannot be pushed into
Disconnected position
Summary of Contents for U-POWER Omega UW-MTX 1.5G
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ......
Page 8: ......
Page 10: ......
Page 12: ...Microswitch...
Page 15: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 27: ......
Page 30: ...3 12 X X 100 150 mm X 100 150 mm X X 15 max...
Page 45: ...3 27 Termination Draw out Breakers THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 46: ...Termination Draw out Breakers 3 28 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 71: ...3 53...
Page 83: ...4 1 4 1 Cradle Mounted Accessories...
Page 84: ...4 2...
Page 85: ...4 3...
Page 86: ...4 4...
Page 87: ...4 5...
Page 88: ...4 6...
Page 89: ...4 7...
Page 90: ...4 8 4 2 Breaker Mounted Accessories...
Page 92: ...4 10...
Page 93: ...4 11...
Page 94: ...4 12...
Page 95: ...4 13...
Page 97: ...Section 5 Protection Control units 5 1 Identification 5 2 Protection Characteristics...
Page 104: ...5 7 Protection Characteristics Overload I T for UW MTX1 0 2 0 1 1 10 100 1000 10000 10s...
Page 119: ...6 3 6 3 Testing Control circuit Interlocks if breaker is equipped with accessories...
Page 134: ......
Page 136: ...7 7...
Page 142: ...Section 8 Useful Hints...