Protection Settings for UW-MTX1.0/1G/1Gi/1.5G/1.5Gi
5.3 Detailed Overview
5-4
Protection: Enable/Disable
Enable
Pick-Up (Ir)= In x …for I2T
1
Delay (tr) in s
12
Pre-alarm
Thermal Memory ON/OFF
OFF
Protection: Enable/Disable
Disable
Pick-Up I
N
= Ir x …
-
-
50%
Pre-alarm
-
Delay (tr) in s
-
-
-
-
-
-
-
-
Protection: Enable/Disable
Enable
I2T ON/OFF
OFF
OFF
Pick- Up, Is = In x…
6In
Delay (ts)
400ms
Pre-alarm
0.6In
1
Protection: Enable/Disable
Pick -up (Ip)=In x…
Protection: Enable/Disable
Disable
Enable
I2T: ON/OFF
Pick- Up (Ig)
= In x…
I2T OFF (tg)
I2T ON (tg)
Pre-alarm
Instantaneous
Earth Fault
0.1-0.2-0.3-0.4-1
0.1-0.2-0.3-0.4
OFF-0.2-0.3-0.4-0.5-0.6
Overload (Neutral)
50%-100%-150%-200%
Same as Overload Phase
Short Circuit
0.6-1-1.5-2-3-4-6-8-10-12
OFF-1.5-2-3-4-6-8-10-12-15
20-100-200-300-400 ms
Factory Settings
Overload (Phase)
OFF- 0.4-0.5-0.6-0.7-0.8-0.85-0.9-0.95-1
0.5-1-2-4-6-12-18-24-30
0.9Ir (fixed)
0.5Is (fixed)
0.8Ig (fixed)
0.8I
N
(fixed)
Parameter
MTX1.0
MTX1.0G
MTX1.5G
-
-
-
10 In
10
x
x
x
Breaker Rating Plug Settings for UW-MTX1.0/1G/1Gi/1.5G/1.5Gi
Note: This symbol indicates that DIP Switch is ON and indicates that DIP Switch is OFF.
CAUTION
Mismatch between actual breaker rating and setting on
the P&C unit will result in error in Protection
Parameters & current measurement displayed .
MTX1Gi
MTX1.5Gi
Inbuilt-ZSI
Short Circuit Enable/Disable
Earth Fault Enable/Disable
-
-
-
-
-
-
x
x
Disable
Disable
Summary of Contents for U-POWER Omega UW-MTX 1.5G
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ......
Page 8: ......
Page 10: ......
Page 12: ...Microswitch...
Page 15: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 27: ......
Page 30: ...3 12 X X 100 150 mm X 100 150 mm X X 15 max...
Page 45: ...3 27 Termination Draw out Breakers THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 46: ...Termination Draw out Breakers 3 28 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 71: ...3 53...
Page 83: ...4 1 4 1 Cradle Mounted Accessories...
Page 84: ...4 2...
Page 85: ...4 3...
Page 86: ...4 4...
Page 87: ...4 5...
Page 88: ...4 6...
Page 89: ...4 7...
Page 90: ...4 8 4 2 Breaker Mounted Accessories...
Page 92: ...4 10...
Page 93: ...4 11...
Page 94: ...4 12...
Page 95: ...4 13...
Page 97: ...Section 5 Protection Control units 5 1 Identification 5 2 Protection Characteristics...
Page 104: ...5 7 Protection Characteristics Overload I T for UW MTX1 0 2 0 1 1 10 100 1000 10000 10s...
Page 119: ...6 3 6 3 Testing Control circuit Interlocks if breaker is equipped with accessories...
Page 134: ......
Page 136: ...7 7...
Page 142: ...Section 8 Useful Hints...