To Configure Analog Settings
Using Web Manager
To configure analog input, go to the
Setup
tab/page and click
Analog Input > Input 1 >
Configuration
in the menu.
Using the CLI
To enter the analog input command level:
enable -> config -> analog -> input
<number>
Using XML
Include in your file:
<configgroup name=”analog input” instance=”1”>
Analog Output
Note:
Analog output is only available on the xSenso 21A2. When output is tracking
input, input is the single source of control. When tracking is disabled, there will be no other
source of control and the state of output is undefined. Instead of leaving it undefined, we
just put it back to startup value which also serves as a safe value to be used when output
is not defined (like during startup output is undefined before any control kicks in).
Table 9-5 Analog Output Settings
Input Settings
Description
Display
Select to enable or disable an output value to be displayed with designated title and
units in the web manager, XML and CLI analog chanel as well as Tunnel and Action
Connect application. You can hide an output by disabling it if you are not using it.
Title
Enter the analog output title as it will appear in web manager, XML and CLI. Leave this
field blank to utilize the default “Output N”, where N is the analog output number. For
example, you can name the reading, “Water Valve”, if a water flow controlling valve is
connected to the xSenso device.
Type
Select type of
Voltage
or
Current
:
Select
Voltage
for an output range from 0 to 10 Volts.
Select
Current
for an output range from 0 to 20 mA.
Startup Value
Enter the
Startup Value
for the initial output value that will be asserted after the device
boots up. This will also take effect when
Analog Input
or
Type
is changed to avoid an
undefined output. This value may subsequently be replaced by a value mapped from
an input channel or by a value specified in an output command.
Analog Input
Select the appropriate
Analog Input
from the drop-down menu to specify the channel
number of the analog input the output will track.
Reading Low
Enter the
Reading Low
value which will be presented as the
Output Low
value.
Output Low
Enter the
Output Low
value which will be converted from the
Reading Low
value.
Reading HIgh
Enter the
Reading HIgh
value which will be presented as the
Output HIgh
value.
Output HIgh
Enter the
Output High
value which will be converted from the
Reading High
value.