Mounting the Switch on Desk or Shelf
1. Verify that the workbench is sturdy and reliably grounded.
2. Attach the four adhesive rubber feet to the bottom of the switch.
Safety Instructions for Rack Mount Installations
The instructions below (or similar) are intended for rackmount installation environments:
1. Elevated Operating Ambient: if installed in a closed or multi-unit rack assembly, the operating ambient
temperature of the rack environment may exceed room ambient. Install the equipment in an environment
compatible with the maximum ambient temperature (Tma) specified.
2. Reduced Air Flow: install the equipment in a rack so that the amount of air flow required for safe operation is
not compromised.
3. Mechanical Loading: Mount the equipment in the rack so that a hazardous condition does not occur due to
uneven mechanical loading (weight distribution/rack balance).
4. Circuit Overloading: consider the connection of the equipment to the supply circuit and the effect that
overloading of the circuits might have on overcurrent protection and supply wiring. Consider all equipment
nameplate ratings when addressing this concern.
5. Reliable Earthing: maintain reliable earthing of rack-mounted equipment; pay particular attention to supply
connections other than direct connections to the branch circuit (e.g., use of power strips).