Operating Manual
General Operating Instructions
97
© Copyright 2016
OMBG3000 – Rev1
5)
Once a parameter has been changed, the left soft key becomes available
to ‘Save and Exit’. Once pressed, the user will be returned to the ‘Settings’
menu.
Note: Alarm settings become active immediately.
Note: When any alarm setting is updated all active alarms will reset.
5.7.1.3
Configure Interface
This option allows the operator to configure the various interface options with
the system to the client’s side. There are three options in this sub-menu:
1)
Configure Analog Outputs
2)
Configure Modbus Slave
3)
Configure Relays
To ‘Exit’ this screen press the right soft key to return to the ‘Settings’ menu.
Configure Analog Outputs
This option allows the user to configure the six 4-20mA analog outputs. The
user can define a gas on any given sample point and set the safe-value that is
output should the customer select this option via the
Note: The safe value is a gas concentration that will force the 4-20mA and
Modbus registers to pre-fixed values. This is to prevent erroneous errors
or alarm conditions in the user’s remote system whilst maintenance is
being performed on the BIOGAS 3000 or any other plant equipment.
1)
From the ‘Configure Interface’ menu press key ‘1’ to select the ‘Configure
Analog Outputs’ option.