72
Operating Manual
OMBG3000 – Iss.01
© Copyright 2016
4.14
Profinet Digital Output
The Profinet option for the BIOGAS 3000 is via a Modbus to Profinet converter
module. The converter is a Profinet slave module and acts as an interface
between the Modbus output of the BIOGAS 3000 and Profinet network.
Warning
The Modbus to Profinet converter module for the
BIOGAS 3000 is not ATEX or IECEx certified and must be
housed in a non-hazardous location or within a
flameproof enclosure. This is the responsibility of the
owner of the equipment.
The BIOGAS 3000 Modbus terminals must only be used
for standard Modbus communications; no other
connections must be made. Connections outside of this
could make the equipment unsafe resulting in a hazard
and invalidate the ATEX/IECEx certification.
Note: The Profinet module can be purchased as a post-sale accessory and
upgraded on site by the user, see LANDTEC part number BG3K.S4 in
BIOGAS 3000 Consumable Products
For wiring to the Modbus terminals from the Profibus module, see section
Configuration of the Profinet Module
4.14.1
The Profinet module can be configured using the GSDML file supplied on the
enclosed CD. Follow the instructions on the supplied installation sheet to
configure the module for the Profinet sub-network.
In addition, the Modbus port on the BIOGAS 3000 must be configured as
followed:
Node Address
1
Baud Rate
9600
Parity
Even
Stop Bits
1
Termination
On
The BIOGAS 3000 acts as a slave.